For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

FC 5105 — Outdoor Storage

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Fire Code § FC 5105

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/518e243f-1f00-49bd-b56a-b302ea505827

Section FC 5105: Outdoor Storage

5105.1 General. The outdoor storage of Level 2 and 3 aerosol products, including storage in temporary storage trailers, shall be separated from exposures in accordance with FC Table 5105.1. FC Table 5105.1 Distance to Exposures for Outdoor Storage of Level 2 and 3 Aerosol Products Exposure Minimum Distance from Aerosol Storage (feet) a Public streets or private roads 20 Buildings 50 Exit discharge to a public street or private road 50 Lot lines 20 Other outdoor hazardous material storage 50 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. The minimum separation distance indicated is not required where exterior walls having a 2-hour fire-resistance rating without penetrations separate the storage from the exposure. The walls shall extend not less than 30 inches above and to the sides of Level 2 and 3 aerosol products.

Ask a question about New York law

Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.