§ 517.44

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 517.44

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/58eac7c1-03ba-4da9-9496-a27cdf70b74b

Section 517.44

Section 517.44 – Revise the opening paragraph in Section 517.44 to read as follows: 517.44 Connection to Equipment Branch. The equipment branch shall be installed and connected to the alternate power source such that equipment described in 517.44(A) is automatically restored to operation at appropriate time-lag intervals following the energizing of the life safety branch. {99:6.7.5.l.4.2(A)} Section 517.44(B) – Revise Item (3) in the list of items in Section 517.44(B) to read as follows: (3) Optional Connections to the Equipment Branch. Additional illumination, receptacles, and equipment shall be permitted to be connected only to the equipment branch.

Ask a question about New York law

Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.