New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 700.31

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/773baed6-9dbe-4d5f-892c-f7dacb252e1f

Section 700.31

Section 700.31 – Revise Section 700.31 to read as follows: 700.31 Ground Fault Protection of Equipment. The alternate source for emergency systems shall not be permitted to have ground fault protection for equipment with automatic disconnecting means. Ground fault indication of the emergency source shall be provided pursuant to 700.6(D).