PC 908 — Relief Vents – Stacks of More than 10 Branch Intervals

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Plumbing Code § PC 908

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/1989ba80-8303-4d11-adc0-eaf495008d8e

Section PC 908: Relief Vents – Stacks of More than 10 Branch Intervals

908.1 Where required. Soil and waste stacks in buildings having more than 10 branch intervals shall be provided with a relief vent at each tenth interval installed, beginning with the top floor. 908.2 Size and connection. The size of the relief vent shall be equal to the size of the vent stack to which it connects. The lower end of each relief vent shall connect to the soil or waste stack through a wye below the horizontal branch serving the floor, and the upper end shall connect to the vent stack through a tee or inverted wye not less than 3 feet (914 mm) above the floor.