Part 2. - Equipment and Systems
a. Standpipes. (1) Required Installations. Not withstanding any other provisions of this Code or Section 905 of the Fire Code of New York State an approved standpipe system(s) shall be provided as herein specified: (2) Building Height. Class III standpipe systems shall be installed throughout all buildings, where the floor level of the highest story is located more than 30 feet above the lowest level of the designated Fire Department vehicle access or where the floor level of the lowest story is located more than 30 feet below the highest level of the designated Fire Department vehicle access. Designated Fire Department vehicle access shall be established by the Fire Chief or the Chief's representative. Exceptions: (i) Class I stand pipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with NFPA. (ii) Class I semi automatic dry standpipes are allowed in open parking garages that are subject to freezing temperatures. A key operated activation device shall be provided at each point of vehicle access into garage. (3) Building Area. In buildings exceeding 10,000 square feet in area per story, Class I automatic wet standpipes shall be provided where any portions of the building's interior area is more than 200 feet of travel vertically and horizontally from the designated point of Fire Department vehicle access. (4) Quantity. In any building the number of standpipes shall be such that all parts of every floor can be reached within 35 feet of a nozzle attached to 100 feet of hose connected to a standpipe. (5) Pipe. All standpipes and automatic sprinkler systems shall be installed in strict compliance with NFPA 14, generally accepted standards and as approved by the Fire Prevention Bureau. Minimum pipe materials and fittings for fire standpipes shall be per NFPA 14. Minimum schedule 40 pipe shall be installed whenever a combined sprinkler/standpipe riser system is proposed. Pipes for all standpipes and sprinkler systems shall be designed so that every pipe is fed by a supply line of at least the same diameter or greater. Pipes run to hose cabinets shall be of a minimum diameter of one and one-half inches. (6) Hose. (i) Standpipes located inside of buildings shall have approved lined hose, (where required) sufficient to reach all parts of the floor, but not in excess of 100 feet, attached to the one-half inch outlet (ii) Such hose shall not be less than one and one-half inches in diameter. (iii) Each line of hose shall be provided with washers at both ends and fitted with an approved nozzle. (iv) Hose shall be kept on approved hose racks or in approved hose cabinets. (7) Water Supply. (i) Not withstanding exception FC Part 2, Subsection a(2)(ii), standpipes shall be supplied under full pressure from an adequate water supply or the water supply shall be furnished automatically by the opening of a hose outlet. (ii) Such water supply shall be furnished by a "street main" in which the pressure is sufficient to maintain a residual pressure as required by NFPA 14 at the most hydraulically remote standpipe while flowing water as described in NFPA 14. (8) Pumps. (i) In buildings requiring a standpipe where the "street mains" cannot maintain a residual pressure as required by NFPA 14 at the top of the most hydraulically remote standpipe an approved fire pump(s) shall be installed in addition to the water supply that is provided, and permanently connected to the required standpipe systems. (ii) The capacities of such pumps shall be sized to maintain the minimum flow rates established in NFPA 14, however the pump shall be not less than 500 gpm. (iii) Such pumps shall have an adequate source of power and shall be supplied in accordance with NFPA 70 and 72. If an emergency power system is required or provided in the building, the fire pump shall be connected to such system. (9) Tests. (i) The fire pump shall be tested in accordance with NFPA 20 and 25. b. Sprinklers. (1) Required Installations. Not withstanding any other provisions of this Code or Section 903 of the Fire Code of New York State, approved automatic sprinkler systems installed in conformity with NFPA 13/13R (as applicable) shall be provided in all buildings herein specified: (i) All new buildings, except as noted below, for which a building permit is issued on or after August 1, 2005. (ii) Conversion of an existing building or portion therein to a more hazardous use group, and including the conversion to an area of public assembly or to a public restaurant, eating or drinking establishment, or cabaret use. (iii) Building addition: including one or more additional stories, or any addition in excess of ten percent of the gross floor area of the existing building, or 1,000 sq. ft. of gross floor area whichever is greater, for which the addition itself shall comply with all of the Provisions of this Section. For any addition in excess of 50 percent of the gross floor area of the existing building (or exceeding 60 percent of the value of the existing building), both the addition and original building shall comply with all of the provisions of this Section. (iv) If the Level 3 provisions of the existing Building Code of New York State apply to an existing building or a portion of an existing building, then the building or portion thereof shall be fully sprinklered in accordance with this Code. (2) Exceptions. The following buildings are not required to have sprinklers systems: (i) One- and two-family detached homes up to two stories. (ii) Open parking garages and structures, for those stories above grade only. (iii) Detached private parking garages, and open public parking garages of one-story in height, conditioned that such structures are used exclusively for parking and contain no cellars nor other uses, including the dispensing of any flammable fuels or liquids. (3) Sprinkler System Design. All sprinkler systems required under this Section shall comply with the following: (i) Sprinklers (or other approved fire suppression system) shall be installed within all areas and throughout all portions of buildings in accordance with NFPA 13/13R (as applicable), including, but not limited to boiler rooms, mechanical rooms, storage rooms, stairways, closets, etc. Sprinklers in stairways shall be located throughout the stairway including all landings and risers. Sprinklers shall not be installed in "dedicated" electrical closets, electrical equipment rooms, electrical switchgear rooms, elevator machine rooms, UPS rooms and battery rooms or any other space where the introduction of water would be considered hazardous. (These locations shall be reviewed with the Commissioner). Note: Battery rooms housing "flooded type" batteries shall be provided with an inert gas suppression system. Exceptions: 1. In Residential Occupancy buildings (R2 & R4), up to four stories, sprinklers shall be installed in all closets and bathrooms that are greater than six square feet in size. In all residential occupancy buildings (R1) and residential occupancies (R2) greater than four stories sprinklers shall be installed in all closets and bathrooms regardless of size. 2. Other exceptions permitted by NFPA may or may not apply in White Plains. Please Confer with Fire Department. (ii) In buildings containing ceiling plenums, a two-tier sprinkler system (or other approved fire-suppression system) shall be installed with heads mounted at both the finished ceiling level, as well as within every ceiling plenum and/or cavity, except that all buildings of fireproof or noncombustible construction shall not be required to have sprinklers within such ceiling plenum/cavities. (iii) All new sprinkler systems shall be of a "fully-supervised" design equipped throughout with both floor valve supervision and main sprinkler valve supervision (for each and all sprinkler valves) connected to the central fire alarm system. (iv) Sprinkler system design drawings shall be submitted for permit prior to the start of any installation work. Designs shall be in accordance with the requirements of the National Fire Protection Association (NFPA). (4) Pipe. (i) Piping shall be ferrous or copper drawn, and shall be designed to withstand when ready for service, a water pressure of not less than 200 pounds per square inch for two hours without leakage at joints, valves, fittings or any part of the piping. Exception: Plastic pipe as defined and approved by the Fire Code of New York State shall be permitted for sprinkler systems in 1 & 2 family houses (R-3) and Residential (R-2 and R-4) occupancies up to four stories. (ii) Minimum schedule 40 pipe shall be installed whenever a combined sprinkler/standpipe riser system is proposed. (5) Valves. Inspector test valves, for testing the most remote sections shall be installed. Such valves may empty to the exterior of the building, or be of the approved interior type. Test valves shall have capped hose threads, to receive a hose for testing. (6) Water Supply. Required sprinkler systems shall be connected to two independent sources of water supply, at least one of which shall be automatic in action. A single connection to the public street main of a reliable water system shall be deemed sufficient when tests indicate an adequate supply is available to the most hydraulically remote sprinklers. (7) Fire Department Connections. (i) Every sprinkler and standpipe system shall be equipped with approved Siamese connections. (ii) There shall be a Siamese connection on each street frontage or, when the building sets back from the street lines, a Siamese shall be provided on each accessible exterior wall. If a frontage or exterior wall, is less than 50 feet in length, no such connection will be required on that frontage if the required Siamese connection is provided on the other frontages. All such Siamese connections shall be interconnected so that the water supply from any source will supply the complete sprinkler system. (iii) Siamese connections shall be identified by color as ordered by the Fire Chief in addition to the regular markings of standpipes, automatic sprinkler, cellar sprinkler, basement sprinklers and wall hydrants. Colors shall be as follows: Sprinklers - Green Standpipe and Wall Hydrants - Red Combination Standpipe and Sprinkler - Yellow Deluge - Blue c. Fire Alarm Systems. (1) Not withstanding any other provisions of this Code or Section 907 of the Fire Code of New York State an approved manual fire alarm system shall be installed within and throughout all areas of the following occupancy groups in accordance with NFPA 72: (i) Parking structures three stories (or 35 feet in height) or greater. d. Fire Alarm and Detection Systems. (1) Required Installations. Not withstanding with any other provisions of this Code or Section 907 of the Fire Code of New York State, an approved manual and automatic fire alarm system with smoke detection capabilities shall be installed as follows: (i) Where work is proposed to be performed in an existing building or areas of existing building that is classified as an alteration "Level 2" as defined in the Existing Building Code of New York State such existing buildings or areas of existing buildings shall be equipped with a fire alarm and detection system with complete area smoke detection in accordance with NFPA 72. (ii) All buildings or structures required to have sprinkler coverage per FC Part 2, Subsection b. shall be equipped with a fire alarm system with complete area smoke detection in accordance with NFPA72. Exceptions: (I) A fire alarm system with smoke detection shall be provided in all R-2 occupancies in common/public corridors, storage rooms, shared amenity spaces, electrical/mechanical rooms etc. Smoke detectors (connected to the building fire alarm system) are not required within the dwelling units. Single/Multiple Station smoke detection shall be provided in each dwelling unit in accordance with the Fire Code of New York State. In addition to multiple station smoke detectors required in dwelling units a minimum of one heat detector shall be provided in each kitchen/kitchenette connected to the building fire alarm system. This provision applies to any R-1, R-2 & R-4 buildings that contain kitchens or kitchenettes. (II) Parking garages. Smoke detection shall not be required in parking areas. (III) Other exceptions permitted by NFPA may or may not apply in White Plains. Please confer with Fire Department. (2) Detector Locations. (i) In general, all areas shall be provided with smoke detection including, but not limited to, corridors, hallways, passageways, storage areas, lobbies, closets, offices, rooms, battery rooms, electrical equipment rooms, mechanical equipment rooms, elevator shafts and elevator machine rooms. (ii) Smoke detection shall be installed within the ceiling cavity of all buildings. Detector spacing shall be approximately one per 5,000 sq. ft. of ceiling cavity space. Exceptions: 1. Buildings equipped with return duct detection in the ceiling plenum shall not require area smoke detection within such plenum. 2. Buildings equipped with a smoke control system so described in The White Plains Smoke Control Code shall not require area detection within such plenum. 3. Ceiling cavities which are inaccessible (e.g. gypsum board ceilings) shall not require smoke detectors. (iii) Heat detection (In lieu of smoke detectors) shall be installed in boiler rooms, janitors closets, kitchens, pantries, and spaces with high or low temperature or other environmental conditions that would preclude the use of smoke detectors. e. Plans and Specifications. Plans and specifications for the installation, extension, modification, alteration or removal from service of any automatic fire, alarm and detection systems shall be submitted to the Division of Fire Prevention and the Department of Building prior to the commencement of any work. f. Smoke Venting of Interior Exitway Stairways. All new enclosed exitway stairways shall be equipped with an approved automatic smoke-actuated roof scuttle vent, or other approved automatic smoke purge system located at the uppermost level. The scuttle shall be activated by a smoke detector. Ambient conditions shall be considered when selecting the type of smoke detection devices. Exception: If the building is required to have a stair pressurization system, smoke venting is not required. g. Alarm Notification. Whenever a fire alarm is activated in any building occupancy (except institutional and others as directed by the Fire Chief), all occupants shall vacate the premises immediately in an orderly fashion. h. Alarm Transmission. Unless otherwise permitted by the Fire Chief all firm alarm systems shall be remotely monitored. i. Adequate Radio Coverage. No person shall erect, construct, maintain, change the use of or construct an addition to any building or structure of Type I or Type II construction which is located more than 75 feet above the lowest level of fire department vehicle access and/or having a floor level more than 30 feet below the lowest level of exit discharge which fails to support adequate radio coverage for the City of White Plains Radio Communications System, including, but not limited to, radio coverage for emergency service workers, firefighters and police officers. j. Equivalent Facilitation. Nothing in this Code is intended to prevent the use of designs or technologies as alternatives to those prescribed in this Code provided they result in substantially equivalent or greater construction, performance etc. The applicant shall provide all technical information requested by the Commissioner so the equivalent facilitations can be evaluated. The Commissioner reserves the right to approve or disapprove any submission at his/her discretion.
Ask a question about White Plains law
Corpus searches the White Plains sections it holds and shows the ones that match, with their citations. Free, no sign-in.