§ 4-18-36 — Standby power supply system

Municipal Code of the City of White Plains, New York (Codified through Ordinance of October 5, 2026. (Supp. No. 79, Update 2)) · White Plains City Code § 4-18-36

Corpus is an independent public-information project, not the official City of White Plains website. Stable reference: corpuslaw.us/code/0c8af291-44c8-4ea5-9ac1-fc73602cbf1c

Sec. 4-18-36. - Standby power supply system.

Every alarm system maintained within the city shall be equipped with a standby power supply system sufficient to maintain the system in a state of readiness to detect the conditions it was installed to monitor for a period of at least four (4) hours in the event of a loss of power supplied by either the public utility power system or the customary power system provided for the premises. Such standby power supply must also retain sufficient power at the end of the four-hour period to successfully transmit a clear signal through an attached automatic alarm communication device if present, or to power local audible or visible signaling devices at rated volume or intensity for a period of at least ten (10) minutes.

(Ord. of 6-2-80, § 3(a))