1507.02. - Bulk petroleum storage.

(a) No person shall erect, construct or replace any bulk storage tanks for the bulk storage of any petroleum products above ground level in the City, except as permitted by the City Zoning Code. All bulk storage tanks hereafter installed aboveground shall be at least fifty feet distant from the property line of the tract of land upon which such storage tanks are located. (b) Aboveground storage tanks shall be provided with a secondary containment area with a minimum capacity of 150% of the rated capacity or be double walled. (c) Aboveground storage tanks shall be protected from damage with 6 inch diameter piping filled with concrete with a minimum of 3 foot spacing on center, with sufficient distance away from the storage tank and painted safety yellow or be protected by other means approved by the Fire Safety Inspector.

(Ord. 22-55. Passed 6-13-22)