1365.07. Containers.
(a) Only A.S.M.E. or D.O.T. containers bearing the U.L. label or the label of some other nationally recognized testing laboratory shall be used in the City. (b) Containers shall meet specifications of the Ohio Unfired Pressure Vessel Code relative to pressure relief valves, general construction and venting. (c) No LP-Gas containers or cylinders shall be located or installed underground. (d) LP-Gas cylinders for salamanders shall be stored outside of buildings. No more than three 100 pound cylinders may be connected up in series to supply a salamander. (e) LP-Gas containers must be equipped with collars or caps to protect valves, whether full or empty. Containers must be mounted on a firm foundation, other than bare ground. (Ord. 682-91. Passed 9-3-91.)