19.52.070 - Pumping Equipment Location Requirements.
No well-casing, pumps, pumping machinery, or suction pipes shall be located in any pit, room, or space extending below ground level, nor in any room or space above the ground which is walled in or otherwise enclosed, unless such rooms, whether above or below ground, have free drainage by gravity to the surface. All floors shall be watertight and sloped from the pump pedestal to the drain, and floors shall extend at least two feet from the well in all directions. The pedestal shall not be less than twelve inches above the floor. This shall not be construed as prohibiting submersible pumps. (Ord. 586, 1970).