§ 15-58 — Sprinkler requirements for business occupancies

Code of Ordinances of the City of Midwest City, Oklahoma (Codified through Ordinance No. 3615, enacted November 13, 2025. (Supp. No. 21)) · Midwest City Code of Ordinances § 15-58

Corpus is an independent public-information project, not the official City of Midwest City website. Stable reference: corpuslaw.us/code/6fae1724-9822-47c1-98f4-beb00b822f8c

Sec. 15-58. - Sprinkler requirements for business occupancies.

Any business occupancy, as defined by the currently adopted version of the International Fire or Building Code, shall be constructed with an automatic sprinkler system and meet all requirements of section 15-25 of this Code when: (1) The total square footage of the structure is thirty thousand (30,000) square feet or more; (2) There is a level or floor within the structure that is below the level of exit discharge; or (3) The building is constructed with a floor or mezzanine above the third floor calculated from the level of exit discharge.

(Ord. No. 2884, § 1, 8-26-03; Ord. No. 3065, § 3, 8-12-08)