§ 15-73 — Sprinkler systems
Code of Ordinances of the City of Midwest City, Oklahoma (Codified through Ordinance No. 3615, enacted November 13, 2025. (Supp. No. 21)) · Midwest City Code of Ordinances § 15-73
Corpus is an independent public-information project, not the official City of Midwest City website. Stable reference: corpuslaw.us/code/745620de-a3fd-49f6-88f6-e6f6f515b9fa
Sec. 15-73. - Sprinkler systems.
(a) The purpose of this section is to provide a consistent, reasonable degree of protection for the life and property from fire through standardization of design, installation and testing requirements for sprinkler systems based upon sound engineering principles, test data and field experience. This section shall be applicable to all new installations, modifications and/or relocations of more than seven (7) sprinkler heads in any structure. All equipment and materials shall be listed as defined in NFPA 13, Chapter 3 (National Fire Protection Association Code for Sprinkler Systems Installation) and acceptable to the appropriate fire official. All services or labor shall be performed only by companies and their employees who are licensed by the Occupational Licensing Division of the Oklahoma State Department of Health. (b) Engineered plans and hydraulic calculations shall be provided to the appropriate fire official prior to any work being performed as specified in subsection (a) of this section. (c) The Midwest City Emergency Operations Center and the appropriate fire official's office must be notified prior to each yearly maintenance of any service being performed on any sprinkler system. The licensed company or contractor shall fully explain the nature of the work to be performed, estimated time of work and whether any portion(s) of any fire protection system will be inoperable during that time. (d) A minimum safety factor of five (5) psi will be required on all new sprinkler system installations. This will be demonstrated in the required hydraulic calculations. Under extreme conditions, the appropriate fire official may increase the safety factor as needed in remote locations or high hazard occupancies. (e) A pressure relief valve shall be installed on all gridded sprinkler systems and so displayed on the submitted engineering plans. (f) All remodel construction projects that involve moving, relocating and/or adding sprinkler heads as specified in subsection (a) of this section shall demonstrate on the submitted plans all existing pipes (by dashed lines), existing outlets, existing heads to remain, heads to be relocated from existing outlets, new heads and plugged outlets. (g) All sprinkler plans submitted shall clearly display fire rated walls and sleeves shall be shown where sprinkler piping penetrates through walls. All rooms shall be labeled accordingly. All construction/sprinkler submittals will be required to display existing city main(s) and size; point of connection into existing city water supplies; flow test information consisting of static pressure, residual pressure, flow in gallons per minute, flow location, day and time; water hydrant(s); underground piping with size(s), length, locations and type of material used in pipe manufacturing. (h) A permit fee of fifty dollars ($50.00) plus the four dollar ($4.00) state fee shall be charged for all newly installed sprinkler systems, plus two cents ($0.02) per square foot of new building construction area. If the project is an interior remodel only and no additional square footage is being added to the structure, only the fifty dollar ($50.00) permit fee and the four dollar ($4.00) state fee will be applicable. All construction documents and fees shall be submitted to the appropriate fire official prior to the inception of any work on-site. (i) Any new or existing structure that, as an option or part of the building requirements, contains a sprinkler system shall not be occupied by customers or employees, stocked or furnished until the sprinkler system has been fully tested, inspected, tagged and a copy of the acceptance test has been received by the appropriate fire official. (j) Any sprinkler system installed as specified in this section shall be monitored off-site, twenty-four (24) hours a day by a monitoring company so designed to receive such signals. (k) A document box shall be provided for all new automatic fire sprinkler systems. (l) All newly constructed building or modifications to existing buildings where an automatic fire sprinkler system is required shall have an exterior access to the control or riser room. (m) Re-inspection fees may be assessed in the event the fifty (50) percent and acceptance test require additional inspections. This fee shall be in the amount of fifty dollars ($50.00).
(Ord. No. 3022, § 8, 6-26-07; Ord. No. 3071, § 2, 10-28-08; Ord. No. 3276, § 12, 7-12-16)
Ask a question about Midwest City law
Corpus searches the Midwest City sections it holds and shows the ones that match, with their citations. Free, no sign-in.