§ 31.30.030 — Fire Chief Authorized to Require Water Supply
Portland City Code (non-zoning titles; Title 33 separately); partial · Portland City Code § 31.30.030
Corpus is an independent public-information project, not the official City of Portland website. Stable reference: corpuslaw.us/code/1fdde3ae-63e1-4d6a-aa2c-eb15f0f7a76a
31.30.030 Fire Chief Authorized to Require Water Supply.
The Fire Chief may establish and enforce standards for water supply for fire protection. Where required by the Fire Chief, a minimum of two fire pumps independently driven must be provided and sized for the sprinkler demand or standpipe demand, whichever is greater.