§ 1011 — STAIRWAYS
The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode B, § 1011
Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/14bb78fc-a895-4cc7-8a57-59368e1966c2
SECTION 1011 STAIRWAYS
* * * 1011.5 Stair treads and risers. * * * 1011.5.2 Riser height and tread depth. * * * [Pursuant to the UCC, delete Section 1011.5.2, Exception 3, and replace as follows:] Exceptions: * * * 3. In Group R-3 occupancies; within dwelling units in Group R-2 occupancies; and in Group U occupancies that are accessory to a Group R-3 occupancy or accessory to individual dwelling units in Group R-2 occupancies; the maximum riser height shall be 8.25 inches (210 mm); the minimum tread depth shall be 9 inches (229 mm); the minimum winder tread depth at the walk line shall be 10 inches (254 mm); and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than 3/4 inch (19.1 mm) but not more than 1.5 inches (38 mm) shall be provided on stairways with solid risers where the tread depth is less than 11 inches (279 mm). * * *