§ 1304 — RECLAIMED WATER SYSTEMS

The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode P, § 1304

Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/8a5a6384-e637-42b0-b88d-f45249064f7d

SECTION 1304 RECLAIMED WATER SYSTEMS

* * * P-1304.2 Water pressure-reducing valve or regulator. Where the reclaimed water pressure supplied to the building exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the reclaimed water distribution or water supply system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section 604.8. 1304.3 Reclaimed water systems. P-1304.3.1 Distribution or water supply pipe. Distribution piping or water supply piping shall comply with Sections P-1304.3.1.1 through P-1304.3.1.3. Exception: Irrigation piping located outside of the building and downstream of a backflow preventer. P-1304.3.1.1 Materials, joints and connections. Distribution piping or water supply piping conveying reclaimed water shall conform to standards and requirements specified in Section 605 for nonpotable water. P-1304.3.1.2 Design. Distribution piping or water supply piping systems shall be designed and sized in accordance with Section 604 for the intended application. P-1304.3.1.3 Labeling and marking. Nonpotable distribution piping or water supply piping labeling and marking shall comply with Section 608.9. * * *

Ask a question about Philadelphia law

Corpus searches the Philadelphia sections it holds and shows the ones that match, with their citations. Free, no sign-in.