E3901 — RECEPTACLE OUTLETS
The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode R, § E3901
Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/4bd15e84-951b-40ba-8358-819114277658
SECTION E3901 RECEPTACLE OUTLETS
* * * [Pursuant to the UCC, delete Section E3901.4.2 and replace as follows:] R-E3901.4.2 Island countertop spaces. At least one receptacle outlet shall be installed at each island countertop space with a long dimension of 24 inches (610 mm) or greater and a short dimension of 12 inches (305 mm) or greater. [210.52(C)(2)] R-E3901.4.2.1 Peninsular countertop space. Not less than one receptacle outlet shall be installed at each peninsular countertop long dimension space having a long dimension of 24-inches (610 mm) or greater and a short dimension of 12 inches (305 mm) or greater. A peninsular countertop is measured from the connected perpendicular wall. [210.52(C)(3)] * * * [Pursuant to the UCC, delete Section E3901.11 and replace as follows:] R-E3901.11 Foyers. Foyers that are not part of a hallway in accordance with Section E3901.10 and that have an area that is greater than 60 ft2 (5.57 m2) shall have a receptacle(s) located in each wall space that is 6 feet (1829 mm) or more in width, but a minimum of one receptacle. Doorways, door-side windows that extend to the floor, and similar openings shall not be considered as wall space. [210.52(H)] * * *