§ 501 — GENERAL

The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode P, § 501

Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/bbad7ee2-eaa9-4701-b98f-bef29b04bd3c

SECTION 501 GENERAL

* * * P-501.9 Thermal expansion control. Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion control device shall be connected to the water heater cold water supply pipe at a point that is downstream of all check valves, pressure reducing valves and backflow preventers. Thermal expansion tanks shall be sized in accordance with the tank manufacturer’s instructions and shall be sized such that the pressure in the water supply system shall not exceed that required by Section P-604.8. * * *