§ 704 — DRAINAGE PIPING INSTALLATION
The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode P, § 704
Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/7efc7894-23b3-45fd-99f8-cdbdae3abc27
SECTION 704 DRAINAGE PIPING INSTALLATION
P-704.1 Slope of horizontal drainage piping. Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than that indicated in Table P-704.1 except that where the drainage piping is upstream of a grease interceptor, the slope of the piping shall be not less than 1/4 inch per foot (2-percent slope). Building sewer force mains are not permitted. TABLE P-704.1 SLOPE OF HORIZONTAL DRAINAGE PIPE SIZE (inches) | MINIMUM SLOPE (inch per foot) 2-1/2 3 or less | 1/4 a 3 4 to 6 | 1/8 a 8 or larger | 1/16 a * * * P-704.5 Dead ends. In the installation or removal of any part of a drainage system, dead ends shall be prohibited. Cleanout extensions and approved future fixture drainage piping shall not be considered as dead ends. * * *