Sec. 14-98. - Operators required.
Licensed operators are required under the following conditions: (1) A boiler operator or stationary engineer shall be in charge of all boilers, stationary engines, prime movers, diesel engines, gas engines, and steam turbines from 30 H.P. to 100 H.P. (2) A stationary engineer or a refrigeration machine operator shall be in charge of all refrigeration equipment and air conditioning equipment over one hundred (100) tons using Group 1 refrigerants; or refrigeration equipment of fifteen (15) tons or more using Group 2 and Group 3 refrigerants as defined in section 14-88(c). (3) A stationary engineer shall be in charge of all boilers, stationary engines, prime movers, diesel engines, gas engines, and steam turbines over 100 H.P. (4) A stationary engineer, boiler operator, or refrigeration machine operator shall be on duty at all times and shall be in the vicinity of the mechanical equipment room and shall not leave the building containing the equipment which they are assigned to watch. For equipment which is monitored by a computer system, refer to section 14-101.
(Ord. 1993, ch. 93-15, § 7, 4-20-93)