§ 4.3 — FIRE RATING FOR EXTERIOR WALLS

Official Code of the City of Clarksville (Supp. No. 110: codified through Ordinance No. 64-2025-26, enacted May 7, 2026) · Clarksville Zoning Ordinance § 4.3

Corpus is an independent public-information project, not the official City of Clarksville website. Stable reference: corpuslaw.us/code/daee940a-1c97-4329-9456-46ea0dd93c3b

4.3 - FIRE RATING FOR EXTERIOR WALLS

Exterior walls of any structure used for residential purposes, located within eight (8) feet or less from any property line, shall have a water/fire resistant gypsum wall board of a minimum ⅝" Type X (or equivalent) on the outside of the exterior wall. This wall board will serve as an underlayment for the exterior siding material. Homes that have continuous exterior soffits shall have the wall board run continuous to the roof deck with fire blocking and be sealed against the deck to prevent the movement of air into the attic space. Gable end vents are prohibited. All other ventilation requirements shall meet the current adopted Building Code. These requirements apply notwithstanding any provision of the current adopted Building Code to the contrary. Variances from this section shall not be granted by the Board of Zoning Appeals.