§ 7-229 — Protection of gas equipment
Municipal Code of the City of Franklin, Tennessee (Codified through Ordinance No. 2026-13, adopted June 23, 2026 (Supp. No. 30)) · Franklin Municipal Code § 7-229
Corpus is an independent public-information project, not the official City of Franklin website. Stable reference: corpuslaw.us/code/590dec8f-a89a-4f72-8f6e-f0194a68ef3a
Sec. 7-229. - Protection of gas equipment.
(1) Guard posts or other means approved by the fire marshal shall be provided to protect gas meters, piping and appurtenances where subject to physical damage or where vehicle traffic is normally expected at the site. (2) Guard posts shall be not less than three feet (0.9m) from the equipment and spaced not more than four feet (1.2m) on center and a minimum of 30 inches (762mm) in height and shall resist a force of 12,000 (53.378N) applied 30 inches above the driving surface. (3) Protective measures may be required and shall be approved by the fire marshal or mechanical official.
(Ord. No. 97-47, § I, 10- -1997; Ord. No. 99-08, § 1, 4- -1999)