§ 11-13 — Required inspections

Code of Ordinances, City of Murfreesboro, Tennessee (Supp. No. 18: codified through Ordinance No. 26-O-38, enacted September 17, 2026) · Murfreesboro City Code § 11-13

Corpus is an independent public-information project, not the official City of Murfreesboro website. Stable reference: corpuslaw.us/code/48f72e61-57e7-495f-adb7-ed764c71e307

Section 11-13 - Required inspections.

Inspections of electrical installations must be conducted as and when required in this section. (A) Underground/Slab Inspection is to be made after trenches or ditches are excavated and conduit is installed and before any backfill or concrete is put in place. (B) Rough-In Inspection is to be made after roof, framing, fire blocking and bracing is in place and electrical wiring is complete and prior to installation of wall or ceiling membranes. At the time of the rough-in inspection, all connections shall be properly made, all raceways must be visible and all junction boxes shall have covers removed. If rough-in is for slab inspection, all conduit must be visible. If the inspection is performed on an existing or remodeled building, all unused wiring and unsafe equipment shall be disconnected and removed before requesting inspection. (C) Final Inspection is to be made after the building is complete, all electrical fixtures are in place and properly connected, and the structure is ready for occupancy. One- and two-family dwellings and townhomes must have temporary power on the structure prior to performing the final electrical inspection. (D) Electrical Safety Inspection (1) To be made prior to reconnection of the service on building where the services have been disconnected due to fire damage or other types of catastrophic occurrences. (2) On buildings where substandard electrical conditions exist. A list of corrections shall be generated and provided to the owner or tenant of the building in question. Permits, inspections and necessary repairs shall be required in accordance with this article. (3) For buildings or at locations which are requesting a Beer Permit be issued. (4) On buildings where deemed necessary by the director to provide for the public safety and welfare. (E) When an electrical inspection is required for the installation of a 36" deep or deeper swimming pool as defined in Code § 7-12 at a residential dwelling, the electrical inspector shall not give final approval for the electrical wiring unless a properly functioning swimming pool alarm has been installed. (F) Service release inspections must be completed prior to temporary service connection to a building or structure.

(Ord. No. 87-21 § 5, 04-23-87; Ord. No. 08-O-48 § 2, 10-23-08; Ord. No. 10-O-41 § 2, 01-13-11; Ord. No. 13-O-59 § 9, 01-16-14; Ord. No. 18-O-71, § 9, 01-17-19)

Ask a question about Murfreesboro law

Corpus searches the Murfreesboro sections it holds and shows the ones that match, with their citations. Free, no sign-in.