For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 32-443 — Installation, testing and maintenance of backflow prevention assemblies

Code of Ordinances of the City of Abilene, Texas (Supp. No. 15: codified through Ordinance No. 85-2026, enacted September 24, 2026) · Abilene Code of Ordinances § 32-443

Corpus is an independent public-information project, not the official City of Abilene website. Stable reference: corpuslaw.us/code/10f2738f-8f4d-40f7-b0db-305c41ec7b8c

Sec. 32-443. - Installation, testing and maintenance of backflow prevention assemblies.

(a) All backflow prevention assemblies must be tested upon installation by a licensed backflow prevention assembly tester and certified to be operating within specifications. Backflow prevention assemblies that are installed to protect against health hazards must also be tested and certified to be operating within specifications at least annually by a recognized backflow prevention assembly tester. (b) Backflow prevention assemblies installed on fire suppression systems must be tested and repaired, as necessary by a backflow prevention assembly tester permanently employed by an approved fireline contractor. (c) Gauges used for backflow prevention assembly testing must be tested for accuracy at least annually in accordance with the AWWA's Manual M14 or the current edition of the University of Southern California's Manual of Cross-Connection Control. A copy of the gauge accuracy test report must be submitted to the City to demonstrate the gauge has been tested for accuracy. (d) A recognized backflow prevention assembly tester must hold a current license from the TCEQ and be registered with the City. (e) All backflow prevention assemblies must be installed and tested in accordance with the manufacturer's instructions, Manual M14 or the University of Southern California's Manual of Cross-Connection Control. (f) Assemblies must be repaired, overhauled, or replaced whenever the assemblies are found to be defective. (g) Original forms recording testing, repairs, and overhaul must be kept and submitted to the City within ten (10) working days of the date of the test, repair or overhaul of each backflow prevention assembly. (h) No backflow prevention assembly or device may be removed from use, or relocated, or other assembly or device substituted for it, without the approval of the City.

(Ord. No. 18-2020, pt. 1(Exh. A), 5-28-20)

Ask a question about Abilene law

Corpus searches the Abilene sections it holds and shows the ones that match, with their citations. Free, no sign-in.