Sec. 18-2-111. - Fire systems.
(a) An approved double check detector backflow prevention assembly (DCDA) shall be the minimum protection on all new fire sprinkler systems using piping material that is not approved for potable water use, and/or that does not provide for periodic flow-through during each 24-hour period. A reduced pressure principle detector backflow prevention assembly (RPDA) must be installed, if any solution other than the potable water can be introduced into the sprinkler system. If the cross-connection inspector determines a chemical loop system can be isolated by installing an RP Assembly at the point of the chemical injection, this, in conjunction with the installation of the DCDA, will be adequate protection. Retrofitting on fire sprinkler systems will be required in each of the following circumstances: (1) Where improper maintenance has occurred; (2) On all high hazard systems; and (3) Wherever an inspector deems necessary. (b) All fireline assemblies will be tested by fireline testers only, however a Customer Service Inspection is required.
(Ord. No. 7585, § 1, 3-1-2016)