For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-453 — Grounding generally

Code of Ordinances, City of Brownsville, Texas (Supp. No. 26: codified through Ordinance No. 2026-1797, enacted January 20, 2026) · Brownsville City Code § 18-453

Corpus is an independent public-information project, not the official City of Brownsville website. Stable reference: corpuslaw.us/code/e7e37d4d-ea8b-463c-968f-fb0ea1bc541e

Sec. 18-453. - Grounding generally.

(a) Where a three-wire 120/240 volts, single-phase service entrance or a four-wire, 120/240 volts, three-phase and a single-phase service entrance receives its supply from an A.C. distribution system, which system is grounded on the low voltage side of the municipal public utilities, the neutral wire of the three-wire, 120/240 volts, two-phase service entrance shall be grounded in the line of the main service entrance switch and the grounding lug provided in the meter socket. No wire of a three-phase, three-wire entrance shall be grounded. No wire of a single-phase, two-wire, 240-volt service entrance shall be grounded. Ground wire shall be of number six gauge (copper) minimum size and shall run continuous from socket to entrance switch to five-eighths inches by eight foot copper weld ground rod. (b) All electrical meter loops in a commercial and residential installation shall be grounded in the following manner: Two driven copper clad rods shall not be less than five-eighths inch by eight feet long and no less than six feet apart or as approved by the Electrical Code.

(Ord. No. 2015-672-H, 4-21-2015)

Ask a question about Brownsville law

Corpus searches the Brownsville sections it holds and shows the ones that match, with their citations. Free, no sign-in.