Sec. 11-106. - Specifications.
(a) Each fire apparatus access roadway shall be constructed and maintained in accordance with the following: (1) The roadway shall have not less than twenty (20) feet of unobstructed width, unless otherwise approved by the fire marshal. (2) Except for one and two family dwellings, the roadway shall be constructed within one hundred (100) feet of maximum hose distance from the nearest point of the fire apparatus access roadway to any given point on the exterior wall of the first story of the building, structure or facility. (3) The roadway shall provide adequate turning radius and turnarounds. (4) The roadway shall be capable of supporting the imposed load of a forty-thousand-pound fire apparatus with two-thirds of the weight on the rear axle. (5) The roadway shall have a minimum of thirteen (13) feet, six (6) inches of vertical clearance. (6) The roadway shall be constructed of concrete, asphalt or other hard surface material approved by the fire marshal. (b) Clearances or widths required by this section may be increased when, in the opinion of the fire marshal, minimum clearances or widths are not adequate to provide fire apparatus access. For high-piled combustible storage, see section 81.109, of the Uniform Fire Code adopted in chapter 29 of this Code.
(Ord. No. 95-260, § II, 12-19-95)
Ask a question about Denton law
Corpus searches the Denton sections it holds and shows the ones that match, with their citations. Free, no sign-in.