Sec. 26-105. - Transformer installation.

(a) Each transformer utilized in underground residential service shall be of the pad-mount type, complete with a high and low tension cable chamber. The high tension chamber shall contain visible disconnection means, a sectionalizing switch for selection of alternate feeders and a no-load tap changing capability. The low voltage chamber shall contain bus facilities for connecting six (6) 120/240 volt service cables, complete with metering facilities. The transformer spade connections shall each contain six (6) lugs with a cable range of No. 4 to No. 2/0 AWG. (b) High and low voltage chambers shall be separated by a metal partition having rigid hinged doors. (c) The transformer shall be placed on a concrete slab installed after underground cables have been installed. The slab shall project a minimum of six (6) inches on all sides of the transformer and shall be six (6) inches thick. Slabs in unstable soil shall be pinned by four (4) piers ten (10) inches in diameter and thirty-six (36) inches deep.

(Code 1966, § 25-120)