§ 18.70.150 — Section R402.4.1.4 Air Leakage Required Certifications, Added

El Paso City Code (Supp. No. 95, Update 4: codified through Ordinance No. 019889, enacted June 23, 2026) · El Paso City Code § 18.70.150

Corpus is an independent public-information project, not the official City of El Paso website. Stable reference: corpuslaw.us/code/aabcd30e-584f-4ae3-a3ae-215ac397e76c

18.70.150 - Section R402.4.1.4 Air Leakage Required Certifications, Added.

R402.4.1.4 Required Certifications. Air leakage testing shall be performed by a third party certified to perform air infiltration testing by a national or state organization approved by the code official. The third party shall not be employed by nor have a financial interest in the entity that constructs the building. Accepted certifications include RESNET Home Energy Rater and Home Field Inspector, Building Performance Institute Infiltration and Duct Leakage professional or Building Analyst certification, and others as approved by the city. R402.4.1.5 Third Party Registration. Approved third party performing air infiltration testing shall be registered with the city.

(Ord. No. 019528, § 1, 8-1-2023)