§ 9.52.080.59 — Section 915.2.3.1 Carbon Monoxide Annunciation in Group E Occupancies, Added
El Paso City Code (Supp. No. 95, Update 4: codified through Ordinance No. 019889, enacted June 23, 2026) · El Paso City Code § 9.52.080.59
Corpus is an independent public-information project, not the official City of El Paso website. Stable reference: corpuslaw.us/code/c659593e-1a28-406c-b2fb-812da62cfd5b
9.52.080.59 - Section 915.2.3.1 Carbon Monoxide Annunciation in Group E Occupancies, Added.
915.2.3.1 Carbon Monoxide Annunciation in Group E Occupancies. Carbon monoxide detection shall be installed in classrooms in Group E occupancies. Carbon monoxide alarm signals shall be automatically transmitted through a Fire Alarm Control Panel annunciator or a Carbon Monoxide Detection Panel annunciator to an on-site location that is staffed by school personnel. A supervisory signal shall be initiated and the signal shall also be transmitted to a Central Station monitoring service. In addition, a local audible alarm with the CO temporal code shall be annunciated in the room of origin.
(Ord. No. 019521, § 1, 7-5-2023)
Ask a question about El Paso law
Corpus searches the El Paso sections it holds and shows the ones that match, with their citations. Free, no sign-in.
