9.52.170.2 - Section C102.1 Minimum number of fire hydrants for a building, Amended.

C102.1 Minimum number of hydrant requirements. The minimum number of hydrants required shall be determined by the fire-flow requirements referenced in Table C102.1, as amended. The requirements regarding the average spacing between hydrants and the maximum distance from any point on street or road frontage to a hydrant are found in IFC Chapter 5 Fire Service Features and Appendix D Fire Apparatus Access Roads. Exception: The fire code official is authorized to accept a deficiency of up to 10 percent where existing fire hydrants provide all or a portion of the required fire hydrant service.

(Ord. No. 019521, § 1, 7-5-2023)