§ 94-256 — Fire protection systems
Code of Ordinances, City of Frisco, Texas (Frisco City Code, Home Rule Charter and Code Appendix current through Ordinance 2026-10-64 adopted October 20, 2026 (eCode360 publication FR6313, scraped 2026-11-18)) · Frisco City Code § 94-256
Corpus is an independent public-information project, not the official City of Frisco website. Stable reference: corpuslaw.us/code/d0feb126-a123-49a3-aaf3-77a691678659
§ 94-256: Fire protection systems.
(a) A double check valve assembly (DCVA) approved by the regulatory authority shall be the minimum protection required for fire sprinkler systems using piping material that is not approved for potable water use and/or that do not provide for periodic flow-through during each twenty-four-hour period, unless a variance has been issued in writing from the regulatory authority. A reduced pressure principle assembly (RPZ) shall be installed when any solution other than potable water can be introduced into the sprinkler system, unless an air gap is used to protect a tank supplying the system. (b) All fire protection backflow devices shall be located in the fire riser room or other location approved by the regulatory authority. Only the regulatory authority shall by written approval grant a variance to this requirement. (c) Upon the approved installation of the DCVA, RPZ or approved backflow prevention assembly, a licensed fire line tester shall complete a cross-connection test report and submit the completed report to the regulatory authority as required by this article. (d) All fire line backflow tester(s) will perform a forward flow test on the backflow assembly before it can be tested. Only the regulatory authority shall by written approval grant a variance to this requirement. (e) All fire line equipment, including piping and valves shall be installed by a state-licensed fire sprinkler system contractor. Only SCR G, RME G, SCR D and RME D (D is for dwelling only not commercial) backflow prevention assembly testers may test and repair assemblies on fire lines if they are full-time employees of an approved fire line contractor. The state fire marshal's office requires that any person performing maintenance on fire lines shall be employed by an approved fire line contractor.
( Ordinance 18-05-24 , sec. 94-2616, adopted 5/15/18 ; Ordinance 2022-04-12 adopted 4/5/2022 )
Ask a question about Frisco law
Corpus searches the Frisco sections it holds and shows the ones that match, with their citations. Free, no sign-in.