For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 13-361 — Local discharge limits

Code of Ordinances, City of Grand Prairie, Texas (Supp. No. 117, Update 1: codified through Ordinance No. 1857-2026, adopted April 27, 2026) · Grand Prairie City Code § 13-361

Corpus is an independent public-information project, not the official City of Grand Prairie website. Stable reference: corpuslaw.us/code/7f2faad8-3241-44b9-8198-8b27f38b75be

Sec. 13-361. - Local discharge limits.

(a) The following pollutant limits are established to protect against pass through and interference and apply at the point where the wastewater is discharged to the POTW. No person shall discharge, or cause or permit to be discharged, wastewater containing in excess of the following instantaneous maximum allowable discharge limits: (1) Toxic pollutants specified in the following table: Toxic Pollutant | TRA Central Instantaneous Maximum Allowable Discharge Limit (mg/L) | TRA Mountain Creek Instantaneous Maximum Allowable Discharge Limit (mg/L) Arsenic | 0.2 | - Cadmium | 0.1 | 0.8 Chromium | 2.1 | - Copper | 1.8 | 1.78 Cyanide | 0.4 | - Lead | 1.2 | 1.0 Mercury | 0.06 | - Molybdenum | 0.5 | - Nickel | 3.3 | - Selenium | 0.2 | - Silver | 0.8 | - Zinc | 6.1 | 2.8 Chlorides | 7,605 Oil and Grease | 200 | 200 pH | 5.5-11.0 S.U. | 6.0-9.0 S.U. All concentrations for metallic substances are for "total" metal unless indicated otherwise. The regulatory authority may impose mass limitations in addition to, or in place of, the concentration-based limitations above.

(Ord. No. 11628-2024, § 1, 10-15-24; Ord. No. 11790-2025, § 2, 10-14-25)

Ask a question about Grand Prairie law

Corpus searches the Grand Prairie sections it holds and shows the ones that match, with their citations. Free, no sign-in.