§ 3.20 — Data center standards

Code of Civil and Criminal Ordinances of the City of Irving, Texas (Irving Code of Civil and Criminal Ordinances, Charter and Land Development Code current through legislation adopted September 24, 2026 (eCode360 publication IR6873, scraped 2026-11-17)) · Irving Land Development Code § 3.20

Corpus is an independent public-information project, not the official City of Irving website. Stable reference: corpuslaw.us/code/39c24be1-c5c9-4481-afb1-4710bf3da1d0

3.20: Data center standards.

3.20.1 Applicability. a) The standards and criteria contained within this section are deemed to be minimum standards and shall apply to all new data centers. b) For this section, "residentially zoned property" shall be any property with a base zoning district of R-15, R-10, R-7.5, R-6, R-ZL, R-ZLa, R-3.5, R-SFA, R-TH, R-2.5, R-MF, R-M F-1, R-MF-2, or TOD. c) New data centers shall be permitted as a principal use by Conditional Use Permit (CUP) only. An application for a CUP shall only be made within the C-W, ML-20, ML-20a, ML-40, ML-120, or C-P districts. d) A Conditional Use Permit is not required for a property zoned for a Site Plan zoning case (S-P-1 or S-P-2) specifically approving a "data center" use prior to the adoption of this ordinance. Such properties still must abide by all other requirements of Section 3.20 or as otherwise stated on the site plan. 3.20.2 Minimum standards - principal use. a) Residential adjacency. 1) Minimum front building setback: 300 feet to nearest property line of residentially zoned property. 2) Minimum side building setback: 300 feet to the nearest property line of residentially zoned property. 3) Minimum rear building setback: 300 feet to the nearest property line of residentially zoned property. [image] 4) Ground-mounted equipment, including but not limited to generators, fuel tanks, cooling equipment, heat exchangers, universal power supply units, or any other outdoor equipment related to the functioning of a data center as a principal use shall be prohibited from being located in any of the following: a. Between a building wall and a public or private street; and b. Within 300 feet of any residentially zoned property. [image] b) Screening: ground-mounted equipment. 1) All ground-mounted equipment shall be fully screened by a masonry wall on all sides. Screening shall be one foot taller than the height of the ground-mounted equipment, or 10 feet tall, whichever is greater. Perforation for ventilation is allowed, provided that the equipment remains fully visually screened. 2) Screening of ground-mounted equipment is not required from adjacent property zoned ML-20, ML-20a, ML-40, ML-120, or C-P, provided that the equipment is at least 300 feet from any residentially zoned property. [image] c) Screening: rooftop equipment. 1) All rooftop equipment shall be fully screened on all sides by an opaque wall. Perforation for ventilation is allowed, provided that the equipment remains fully visually screened. 2) Screening shall be one foot taller than the height of the rooftop equipment or five feet tall, whichever is greater. d) Height. 1) Maximum height: 75 feet. 2) For the purposes of this section, "maximum height" shall be measured at top plate and shall exclude any parapets, rooftop screening or equipment. e) Lighting. 1) Concealment and shielding. Light sources shall be concealed or shielded with luminaries containing shielding, skirts, or cut-offs with a cutoff angle not exceeding 90 degrees to minimize the potential for glare and unnecessary diffusion on adjacent property. For purposes of this requirement, the angle shall be measured using a line drawn from the direction of light rays at the light source or reflector, and a line perpendicular to the ground from the light source above from which no light is emitted. [image] 2) Glare prohibited. Lighting shall not cast glare onto adjacent lots or streets in any way that decreases the safety of pedestrians and vehicles. 3) Maximum spillover. In no case shall exterior lighting add more than one footcandle to illumination levels at any point off-site. 4) Uplighting. Light fixtures used to illuminate flags, statues, or any other objects mounted on a pole, pedestal, or platform shall use a narrow cone beam of light that will not extend beyond the illuminated object. 5) Building-mounted fixtures. Building-mounted light fixtures shall be attached to walls, and the top fixture shall not be lower than 10 feet or higher than 18 feet above finished grade, except entry/exit lighting positioned above the entry/exit. 6) Security lighting. Any exterior lighting device (luminaire) designed for security lighting shall be protected by weather- and vandal-resistant covering, be a managed light source, and directed down to minimize glare and intrusiveness. 7) Height of fixtures. Freestanding light fixtures shall not exceed 20 feet in height within 50 feet of any residential zoning district, 25 feet in height within 50 to 150 feet of any residential zoning district, and 35 feet in all other locations. For the purposes of this requirement, height shall be measured from the top of a light fixture to the adjacent grade at the base of the support for that light fixture. 3.20.3 Minimum standards-accessory use. a) Size. Data centers used as an accessory use may not exceed 1,000 square feet. b) Maximum height. 15 feet. c) Location. 1) May not be located in any required front, side or rear setback; 2) May not be located between a principal building and a public or private street; and 3) May not be located within 50 feet of residentially zoned property. d) Accessory equipment. Cooling systems, uninterrupted power supplies (UPSs), and other associated equipment shall be contained within the container or structure of the accessory data center and/or the principal building on the site. Any backup generators and fuel tanks shall comply with the setback and screening standards in Section 3.20.2a) and Section 3.20.2b). e) Screening. The accessory data center shall be fully screened on all sides by a solid masonry wall. 1) The screening wall shall be a minimum height of one foot taller than the data center structure. 2) Perforation for ventilation is allowed, provided that it remains fully visually screened.

( Ordinance 2024-10938 , § 13, adopted 6/27/2024 ; Ordinance 2025-11063 adopted 2/6/2025 )

Ask a question about Irving law

Corpus searches the Irving sections it holds and shows the ones that match, with their citations. Free, no sign-in.