For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 5-94.5 — Amendments to the International Fire Code 2021 Edition

Code of Ordinances of the City of Lewisville, Texas (Supp. No. 34: codified through Ordinance No. 0854-26-ORD, adopted July 6, 2026) · Lewisville City Code § 5-94.5

Corpus is an independent public-information project, not the official City of Lewisville website. Stable reference: corpuslaw.us/code/0393ac11-ea6c-42e5-8d67-037b42e06d90

Sec. 5-94.5. - Amendments to the International Fire Code 2021 Edition.

The city adopts the following revisions and additions to the International Fire Code 2021 Edition adopted by this article: Section 101.1; change to read as follows: 101.1 Title. These regulations shall be known as the Lewisville Fire Code, hereinafter referred to as "this code." Section 101.2.1; change to read as follows: 101.2.1 Appendices. All appendices, except appendices A, J, and M, as published in the International Fire Code, 2021 Edition, are adopted in their entirety. Section 102.1; #3; change to read as follows: 3. Existing structures, facilities and conditions when required in Chapter 11 or in other specific sections of this code. Section 102.3; change to read as follows: 102.3 Change of use or occupancy. A change of occupancy shall not be made unless the use or occupancy is made to comply with the requirements of this code, the International Building Code, and the International Existing Building Code. Section 102.7.3; add this section to read as follows: 102.7.3 Alternative editions of referenced codes and standards. The fire code official is authorized to utilize newer additions of the referenced standards listed in Chapter 80. Section 103.1; change to read as follows: 103.1 Creation of agency. The Lewisville Fire Marshal's Office is hereby created and the official in charge thereof shall be known as the fire code official. The function of the agency shall be the implementation, administration and enforcement of the provisions of this code, and the fire marshal shall be known as the fire code official. Section 104.7; delete in its entirety. Section 104.7.1; delete in its entirety. Section 105.3.3; change to read as follows: 105.3.3 Occupancy Prohibited before Approval. The building or structure shall not be occupied prior to the fire code official issuing a permit when required and conducting associated inspections indicating the applicable provisions of this code have been met. Section 105.6.25; add this new section to read as follows: 105.6.25 Electronic access control systems. Construction permits are required for the installation or modification of an electronic access control system, as specified in Chapter 10. A separate construction permit is required for the installation or modification of a fire alarm system that may be connected to the access control system. Maintenance performed in accordance with this code is not considered a modification and does not require a permit. Section 107.2: amend to read as follows: 107.2 Schedule of permit fees. A fee for each permit shall be paid as required in accordance with Section 2-201 of the Code of Ordinances of the City of Lewisville. Section 107.3; delete section in its entirety. Section 111.1; amend to read as follows: Section 111.1 Means of Appeal—Permitted Applications. An applicant may appeal a fire code official's denial, disapproval, revocation, or other refusal to grant the applicant's submitted permit application. Such an appeal must be filed in writing with the City Manager within thirty (30) days after the date of the denial, disapproval, refusal, and/or revocation. The appeal must also state how the fire code official allegedly misconstrued or wrongly interpreted the fire code. After receiving an appeal in accordance with this section, the City Manager shall submit the appeal to the City Council for their consideration. The City Council shall act as the Board of Appeals, and their decision on the appeal shall be the final decision. Section 111.1.1; add this new section to read as follows: 111.1.1 Means of Appeals—All Other Actions of the fire code official. An individual directly affected by any order, decision, or determination made by the fire code official relative to the application and interpretation of this code which is not addressed in Section 111.1, above, may appeal the fire code official's decision. For all such appeals, the process shall be promulgated by the fire code official. Section 111.3; delete section in its entirety. Section 111.4; delete section in its entirety. Section 112.3; add exception to read as follows: Exception: Citations for violations of this code may be issued without requiring the issuance of a notice. Section 112.3.3; amend to read as follows: 112.3.3 Prosecution of violations. If a notice of violation is issued and is not complied with promptly, the fire code official is authorized to request the legal counsel of the jurisdiction to institute the appropriate legal proceedings at law or in equity to restrain, correct, or abate such violation or to require removal or termination of the unlawful occupancy of the structure in violation of the provisions of this code or of the order or direction made pursuant thereto. Section 112.4; delete in its entirety. Section 113.2; amend to read as follows: Section 113.2 Issuance. The stop work order shall be in writing and shall be given to the owner of the property, the owner's authorized agent or the person performing the work. If no one is present at the time of issuance, a stop work order shall be posted on or near the front entrance of the structure, or on the fire protection system where work shall stop. Upon issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the order and the conditions under which the cited work is authorized to resume. Section 114.4; amend to read as follows: 114.4 Notice. If an unsafe condition is found, the fire code official shall serve on the owner of the structure or the owner's authorized agent a written notice that describes the condition deemed unsafe and specifies the required repairs or improvements to be made to abate the unsafe condition. Section 114.5; amend to read as follows: 114.5 Method of Service. Such notice shall be deemed properly served in accordance with one of the following methods: 1. A copy is delivered to the owner personally. 2. A copy is sent by certified mail addressed to the owner at the last known address with return receipt requested. 3. A copy is posted on or near the front door of the structure. 4. A copy is delivered in any other manner as prescribed by law. Section 201.4, amend to read as follows: Where terms are not defined through the methods authorized by this section or by section 1-2 of the Lewisville City Code, such terms shall have ordinarily accepted meanings such as the context implies. Merriam-Webster's Collegiate Dictionary, 11th Edition, shall be considered as providing ordinarily accepted meanings. In the event of a conflict between the definition of a term in this code and in section 1-2 of the Lewisville City Code, this code shall prevail. Section 202; change to amend and add those definitions as set forth below: [B] AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing, or similar care on a less than 24-hour basis to persons who are rendered incapable of self-preservation by the services provided. This group may include but not be limited to the following: - Dialysis centers - Providers of procedures involving sedation - Providers of sedation dentistry - Surgery centers - Colonic centers - Psychiatric centers [B] ATRIUM. An opening connecting three or more stories other than enclosed stairways, elevators, hoistways, escalators, plumbing, electrical, air-conditioning or other equipment, which is closed at the top and not defined as a mall. Stories, as used in this definition, do not include balconies within assembly groups or mezzanines that comply with Section 505 of the International Building Code. [B] DEFEND IN PLACE. A method of emergency response that engages building components and trained staff to provide occupant safety during an emergency. Emergency response involves remaining in place, relocating within the building, or both, without evacuating the building. FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks …[remainder of text unchanged]… HIGH-PILED COMBUSTIBLE STORAGE: add a second paragraph to read as follows: Any building classified as a group S Occupancy or Speculative Building exceeding 3,600 sq. [ft.] that has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage. When a specific product cannot be identified, a fire protection system and life safety features shall be installed as for Class IV commodities, to the maximum pile height. HIGH-RISE BUILDING. A building with an occupied floor located more than 55-feet above the lowest level of fire department vehicle access. OCCUPANCY CLASSIFICATION. Business Group B, add: Fire Stations—if protected with an automatic smoke detection system as specified in Section 907.2.10.2 and emergency escape and rescue windows in the sleeping areas as specified in the International Building Code section 1030. Police Stations with detention facilities for 5 or less. OWNER. Any person, agent, operator, entity or firm having any legal or equitable interest in the property; or recorded in the official records of the state, county or municipality as holding an interest or title to the property; or otherwise having possession or control of the property, including the guardian of the estate of such person if ordered to take possession of real property by a court. REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles, motorcycles, recreational vehicles, and watercraft. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement and other such minor repairs. SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Chief or Fire Marshal. When utilized, the number required shall be as directed by the Fire Chief or Fire Marshal. Charges for utilization shall be as normally calculated by the jurisdiction. STRIP MALL BUILDING. A single building, of two or less floors, enclosing a number of tenants and occupants such as retail stores, drinking and dining establishments, offices, or other similar uses each tenant of which shall have a separate exit directly to the exterior of the building. UPGRADED OR REPLACED FIRE ALARM SYSTEM. A fire alarm system that is upgraded or replaced includes, but is not limited to the following: • Replacing one single board or fire alarm control unit component with a newer model • Installing a new fire alarm control unit in addition to or in place of an existing one • Conversion from a horn system to an emergency voice/alarm communication system • Conversion from a conventional system to one that utilizes addressable or analog devices. The following are not considered an upgrade or replacement: • Firmware updates • Software updates • Replacing boards of the same model with chips utilizing the same or newer firmware. Section 307.1.1; change to read as follows: 307.1.1 Prohibited open burning. Open burning is prohibited within the city limits. EXCEPTIONS: 1. Open burning for the purpose of reducing the impact of wildland fire when authorized by the fire code official by permit described in Section 307.2. 2. Open burning on government owned/managed property for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests when prior written notice of such open burning is provided to the fire marshal at least one month prior to the burn and the open burn complies with all federal, state, and local laws, guidelines, restrictions, and/or bans. Section 307.2; change to read as follows: 307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling a fire for reducing the impact of wildland fire. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. A permit may not be granted unless the proposed burn complies with all federal, state, and local laws, guidelines, restrictions, and/or bans. Examples of state or local law, or regulations referenced elsewhere in this section may include but not be limited to the following: 1. Texas Commission on Environmental Quality guidelines and/or restrictions. 2. State, County, or Local temporary or permanent bans on open burning. 3. Local written policies as established by the fire code official. Section 307.3; change to read as follows: 307.3 Extinguishment authority. The fire code official is authorized to order the extinguishment of any open burning by the permit holder, another person responsible or the fire department, whether a valid permit is obtained or not, that creates or adds to a hazardous or objectionable situation. Section 307.4; change to read as follows and delete all exceptions: 307.4 Location. The location for open burning shall not be less than 300 feet from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet of any structure. Section 307.4.1; change to read as follows: 307.4.1 Bonfires. Bonfires are prohibited inside City limits. Section 307.4.2; change to read as follows: 307.4.2 Recreational Fires. Recreational fires are prohibited within the City limits. Section 307.4.4; add this new section to read as follows: 307.4.4 Permanent outdoor firepit. Permanently installed outdoor firepits for recreational fire purposes shall not be installed within 10 feet of a structure or combustible material. Exception: Permanently installed outdoor fireplaces constructed in accordance with the International Building Code. Section 307.4.5; add this new section to read as follows: 307.4.5 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2. Section 307.4.5.1; add this new section to read as follows: 307.4.5.1 Approvals. All outdoor burning must utilize a mechanical trench/pit burning assembly approved by the Texas Commission on Environmental Quality (TCEQ). All applicants must obtain approval through the TCEQ for the site specific burning in the city. Section 307.4.5.2; add this new section to read as follows: 307.4.5.2 Materials. Burning shall include only materials authorized on an approved burning permit for the purpose of clearing land for future development. Section 307.4.5.3; add this new section to read as follows: 307.4.5.3 Location. Areas for burning shall be located a minimum distance of 1,800 feet from all structures downwind and 500 feet from any other structures not classified as being downwind. In addition, areas for burning shall be located a minimum distance of 500 feet from wooded areas, roadways, and overhead power lines. Surrounding grass and/or brush must be mowed or maintained as to not present a fire hazard. Section 307.4.5.4; add this new section to read as follows: 307.4.5.4 Other Materials. No fuel storage tank or other hazardous material is to be stored within the burn area. Section 307.4.5.5; add this new section to read as follows: 307.4.5.5 Requirements. Each day, after 8:00 a.m., prior to any permitted burning operation, the below listed agencies must be contacted: • TCEQ 817-588-5800 Ask for Air Quality Person • Fire Marshal's Office, 972-219-3462 1. Hours of burning shall be between 8:00 a.m. and 5:00 p.m. Monday through Friday. On ozone action days, burning shall not begin before 10:00 a.m. The pit shall be covered with dirt and completely extinguished by 5:00 p.m. each day. No smoke or burning objects shall be visible. 2. No burning allowed on holidays or weekends. 3. Approved stand-by equipment must be on location and shall include at least one piece of earth moving equipment (bulldozer, backhoe, track loader, etc.). 4. All burning must be constantly attended by at least one competent person on location to operate stand-by equipment, and all fires shall be completely extinguished by 5:00 p.m. or before being left alone. 5. Wind velocity for below ground pit/trench burning operation shall not exceed 20 miles per hour. Section 307.4.5.6; add this new section to read as follows: 307.4.5.6 Failure to Comply. Burning permits will be revoked for failure to comply with any of the following: 1. Violation of any site specific or general rules regulating burning. 2. Extreme dry weather. 3. Change in wind direction. 4. If in the case that ash, excessive smoke, or excessive odor is documented by fire prevention in relation to any surrounding property for whatever reason. 5. Where any life, health, nuisance, or other hazard is indicated to surrounding persons or property. Note: If permits are revoked by fire prevention for any of the reasons listed above, materials shall be disposed of in a different manner. Further information may be obtained by contacting the Fire Marshal's Office weekdays at (972) 219-3462. Section 307.5; change to read as follows: 307.5 Attendance. Trench burns and the use of portable outdoor fireplaces shall be constantly attended until the... (Remainder of section unchanged) Section 308.1.4; change to read as follows and delete exception 3: 308.1.4 Open-flame cooking devices. Open-flame cooking devices, charcoal grills and other similar devices used for cooking shall not be located or used on combustible balconies, decks, or within 10 feet of combustible construction. Exceptions: 1. One- and two-family dwellings, except that LP-gas containers are limited to a water capacity not greater than 50 pounds [nominal 20 pound LP-gas capacity] with an aggregate LP-gas capacity not to exceed 100 lbs. (5 containers). 2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system, except that LP-gas containers are limited to a water capacity not greater than 50 pounds [nominal 20 pound LP-gas capacity], with an aggregate LP-gas capacity not to exceed 40 lbs. (2 containers). Section 308.1.6.2, Exception #3; change to read as follows: 3. Torches or flame-producing devices in accordance with Section 308.1.3. Section 308.1.6.3: change to read as follows: Sky lanterns. A person shall not release or cause to be released unmanned free-floating devices containing an open flame or other heat source, such as but not limited to a sky lantern. Section 310.1.1; add this new section to read as follows: 310.1.1 Definitions. Administrative area means the area of an establishment not generally accessible to the public, including, but not limited to individual offices, stockrooms, and employee lounges, or meeting rooms. Bar means an establishment licensed by the state for the sale of alcoholic beverages which derives more than 75 percent of its annual gross sales from the sale of alcoholic beverages for on-premises consumption. Cigar bar means an establishment used primarily for the sale of cigars, cigar- related products, and alcoholic beverages, which generates at least fifteen (15) percent of its gross revenues from the sale of cigars and cigar related products, does not allow admittance to or employ persons under the age of eighteen (18), and is equipped with a commercial walk-in humidor with a humidifier which maintains a set humidity through evaporation and diffusion and is connected to a reverse osmosis filtration system for constant water supply. Sale of food products is permitted. Director means the director of the department designated by the city manager to enforce and administer this ordinance or the director's designated representative. Food products establishment means any fixed or mobile restaurant, coffee shop, cafeteria, short order cafe, luncheonette, grill, tea room, sandwich shop, soda fountain, confectionery, ice cream store, refreshment stand, fruit stand, country club, catering service, industrial feeding establishment, or grocery store; private or public where food or drink is prepared for sale or for service on the premises or elsewhere; and any other eating or drinking is prepared for sale or for eating or drinking establishment or operation where food or drink is served or provided for the public with or without charge. Health care facility means any institution that provides medical, surgical, or overnight facilities for patients. Retail and service establishment means any establishment which sells goods or services to the general public. Public service area means any area to which the general public routinely has access for municipal services or which is designated a public service area in a written policy prepared in compliance with this ordinance. Sign means the official placard designating an area or facility where smoking is prohibited, and must conform to one of the following choices of wording, to-wit: 1. No smoking; 2. The universal symbol for no smoking; or 3. Any other language indicating that the area marked is designated as a nonsmoking area. All signs must be of sufficient size to accommodate the message contained thereon in letters at least one inch in height. Section 310.1.2; add this new section to read as follows: 310.1.2 Smoking prohibited in certain public areas. (a) A person commits an offense if he smokes or possesses a burning tobacco, weed, or other plant product in any of the following: (1) A public library, or museum; (2) Hearing rooms, conference rooms, meeting rooms or any public service area of any facility owned, operated, or managed by the city in which public business is conducted, when the public business requires or provides an opportunity for direct participation or observation by the general public; (3) Every publicly or privately owned theater, auditorium, or other enclosed facility which is open to the public for primary purpose of exhibiting any motion picture, stage drama, musical recital, athletic event, or any other performance or event, in all areas except either in that area commonly known as the lobby, or in areas not open to the public; (4) An elevator used by the public; (5) Any retail or service establishment serving the general public, including, but not limited to any department store, grocery store, or drug store; (6) Any food product establishment; (7) Any bar, including a bar within a food product establishment; (8) In or within 15 feet of any door, operable window/vent or other opening to a place where smoking is prohibited, except as provided for in section 310.1.4, below; (9) Hotels and motels, except as provided for in section 310.1.4, below; or (10) Bowling centers. (b) The owner or person in control of an establishment or area designated in subsection (a) of this section shall post a conspicuous sign at the main entrance to the establishment or area. (c) The owner or person in control of an establishment or area regulated by this section commits an offense if he fails to: (1) Post a sign in accordance with subsection (b) of this section; (2) Advise a person who violates this section that smoking is not allowed; or (3) Request a person to remove himself from the location after that person has been advised that smoking is not allowed and that person willfully continues to smoke. (d) It shall be a defense to prosecution under this section that the establishment or area in which the offense takes place does not have displayed a conspicuous sign that smoking is prohibited. Section 310.1.3; add this new section to read as follows: 310.1.3 Regulation of smoking—Workplace, schools, health care facilities. Notwithstanding the provisions of this ordinance, any employer, primary or secondary school administrator, or health care facility provider may designate any building, or portion thereof, as a nonsmoking area. Any employer, primary or secondary school administrator, or health care facility provider who chooses to designate any building, or portion thereof, as a nonsmoking area shall: (a) Adopt, implement, and maintain a written smoking policy which shall be communicated to all employees at least three weeks prior to its adoption; (b) Prominently display reasonable sized signs that smoking is prohibited; and (c) Provide facilities in sufficient numbers and at such locations to be readily accessible for the extinguishment of smoking materials. Section 310.1.4; add this new section to read as follows: 310.1.4 Exceptions. The following areas are exempted from the provisions of this ordinance: (a) A retail or service establishment which derives more than 50 percent of its annual gross sales from the sale of tobacco, tobacco products, or smoking implements. (b) An administrative area within the workplace. (c) An unenclosed outdoor seating area associated with a food product establishment, so long as: (1) Smoking is prohibited in or within 15 feet of any door, operable window/vent or other opening to a place where smoking is prohibited; (2) The outdoor seating area is not adjacent to a playground or play area for children; or (3) The outdoor seating area is not posted as a nonsmoking area by the owner, operator or person in control of the establishment. (d) Not more than ten percent of hotel and motel rooms rented to guests and designated as smoking rooms. All smoking rooms on the same floor must be contiguous and smoke from these rooms must not infiltrate into areas where smoking is prohibited under provisions of this ordinance. The status of rooms as smoking or nonsmoking may not be changed, except to add additional nonsmoking rooms. (e) A cigar bar. Section 311.5; change to read as follows: 311.5 Placards. The fire code official is authorized to require marking of any vacant or abandoned buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural or interior hazards, as required by Section 311.5.1 through 311.5.5. Section 319.10.3.1; add this new section to read as follows: 319.10.3.1 Fuel gas system testing. Fuel gas systems installed on mobile food preparation vehicles shall installed in accordance with this code, the International Fuel Gas Code, and the Railroad Commission of Texas Rules. Fuel gas systems shall be pressure tested by a technician certified by the Railroad Commission of Texas in the appropriate fuel. Section 403.4; change Section 403.4to read as follows: 403.4 Group E Occupancies. An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for Group E occupancies and for buildings containing both a Group E occupancy and an atrium. A diagram depicting two evacuation routes shall be posted in a conspicuous location in each classroom. Group E occupancies shall also comply with Sections 403.4.1 through 403.4.3. Section 404.2.2; add Number 4.10 to read as follows: 4.10 Fire extinguishing system controls. Section 405.4; change Section 405.4 to read as follows: 405.4 Time. The fire code official may require an evacuation drill at any time. Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire. Section 501.4; change to read as follows: 501.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed for any structure or development, they shall be installed, tested, and approved prior to the time of which construction has progressed beyond completion of the foundation of any structure. Section 503.1.1; change to read as follows: 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45,720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Except for one- or two-family dwellings, the path of measurement shall be along a minimum of a ten feet (10') wide unobstructed pathway around the external walls of the structure. [Exceptions remain unchanged] Section 503.2.1; change to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet, exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet. For buildings exceeding 30 feet in height, see appendix Section D105. Exceptions: 1. Vertical clearances may be reduced with the approval of the fire code official provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance. 2. Minimum widths may be reduced with the approval of the fire code official when site conditions prohibit constructing or maintaining required widths. Fire apparatus access roads shall be constructed to accommodate the imposed load of 85,000 GVW of fire apparatus. Section 503.2.2: change to read as follows: 503.2.2 Authority. The Fire Code Official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. Section 503.2.3; change to read as follows: 503.2.3 Surface. Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus (minimum 85,000 GVW) and shall be provided with an all-weather paved driving surface. Paved driving surface as used in this section shall mean reinforced concrete or asphalt sufficiently designed to support any fire department vehicle and surface capable of being striped as a fire lane. Section 503.2.4; change to read as follows: 503.2.4 Turning radius. The turning radius of a fire apparatus access road shall be approved by the fire code official. The minimum inside turning radius of a fire apparatus access road shall be 20 feet. The minimum outside turning radius of a fire apparatus access road shall be 44 feet. Section 503.3; change to read as follows: 503.3 Marking. Striping, signs, or other markings, when approved by the fire code official, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Striping, signs and other markings shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. 1. Striping - Fire apparatus access roads shall be continuously marked by painted lines of red traffic paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the striping shall be on the vertical face of the curb. 2. Signs - Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (6'6") above finished grade. Signs shall be spaced not more than fifty feet (50') apart along both sides of the fire lane. Signs may be installed on permanent buildings or walls or as approved by the fire code official. Section 503.4; change to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times. Section 505.1; change to read as follows: Section 505.1 Identification. (a) Owners of single-family, two-family, multi-family dwellings, commercial and industrial structures in the city are required to place or have placed, the proper street number, building number, suite and/or unit number, in a designated location so that same can be plainly seen and read from the street and alley, when alleys are provided. Street numbers will be designated by the director of Neighborhood Services or his designee. Building numbers, suite and/or unit numbers for multi-family and commercial structures shall be submitted to the city for approval by the owner or developer. (b) Where the owner is a nonresident of the city, the duty outlined in subsection (a) of this section shall devolve on the occupant or agent of the owner of such structures. Section 505.1.1; add this new section to read as follows: Section 505.1.1 Size and location of numbers. (a) One and two family dwellings; numbers shall be a minimum three inches high, posted front and rear when rear access is available. Numbers shall be posted on the principal structure at a minimum height of five feet above existing grade. Numbers may also be posted on curbside mailboxes when available. Numbers shall be posted on a contrasting background and maintained clearly visible from the street and alley, when rear access is available. (b) Multi-family dwellings; building numbers shall be a minimum 12 inches high, unit range numbers shall be minimum four inches and unit numbers shall be a minimum three inches high. Building and unit range numbers shall be posted on two sides of every building. Location of building numbers and unit range numbers shall be designated by the fire marshal. Individual unit numbers shall be posted a minimum five feet above existing grade. All numbers shall be posted on a contrasting background and maintained clearly visible as defined by the fire marshal. (c) Commercial and industrial structures; all street numbers, suite or lease space numbers shall be a minimum of six inches high, posted front and rear when rear access is available. All numbers shall be posted on a contrasting background and maintained clearly visible as defined by the fire marshal. Section 505.1.2; add this new section to read as follows: Section 505.1.2 Display of numbers. (a) All numbers for new construction shall be fixed and properly displayed as required by this article at the time the building, lease space, suite or unit is released for occupancy. (b) All numbers for existing buildings, lease space, suites or units shall be fixed and properly displayed after notification to the owner/occupant. A reasonable time, to be determined by the director of community development, will be granted for purposes of compliance. Section 507.2.3; add new section to read as follows: 507.2.3 Connections to public water mains. Two separate isolated points of connection to the public water main, forming a grid arranged and valved so that no single obstruction to the water system will shut-off the water supply for any hydrants or fire sprinkler system, shall be required when any of the following conditions exist: 1. Whenever a newly constructed building exceeds 35,000 square feet, or 2. Whenever three or more on-site fire hydrants are required, or 3. A dead-end fire water main exceeds 300 feet in length. Section 507.4; change to read as follows: 507.4 Water supply test date and information. The water supply test used for hydraulic calculation of fire protection systems shall be conducted in accordance with NFPA 291 "Recommended Practice for Fire Flow Testing and Marking of Hydrants" and within one year of sprinkler plan submittal. The fire code official shall be notified prior to the water supply test. A permit shall be obtained from the Fire Prevention Division for water supply tests and shall be witnessed by the fire code official, as required. The exact location of the static/residual hydrant and the flow hydrant shall be indicated on the design drawings. All fire protection plan submittals shall be accompanied by a hard copy of the waterflow test report, or as approved by the fire code official. The report must indicate the dominant water tank level at the time of the test and the maximum and minimum operating levels of the tank, as well, or identify applicable water supply fluctuation. The licensed contractor must then design the fire protection system based on this fluctuation information, as per the applicable referenced NFPA standard. Reference Section 903.3.5 for additional design requirements. Section 507.5.2; change to read as follows: 507.5.2 Inspection, testing and maintenance. Fire hydrant systems shall be subject to periodic tests as required by the fire code official. Fire hydrant systems shall be maintained is an operative condition at all times and shall be repaired where defective. Additions, repairs, alterations and servicing shall comply with approved standards. Records of tests and required maintenance shall be maintained and submitted to the fire code official using a process promulgated by the fire code official. Section 507.5.4; change to read as follows: 507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. Section 509.1.2; add new Section 509.1.2 section to read as follows: 509.1.2 Sign Requirements. Unless more stringent requirements apply, lettering for signs required by this section shall have a minimum height of 2 inches (50.8 mm) when located inside a building and 4 inches (101.6 mm) when located outside, or as approved by the fire code official. The letters shall be of a color that contrasts with the background. Section 605.4.1, 605.4.1.1 and 605.4.2.2; change to read as follows: 605.4.1 Fuel oil storage in outside, above-ground tanks. Where connected to a fuel-oil piping system, the maximum amount of fuel oil storage allowed outside above ground without additional protection shall be 660 gallons (2,498 L). The storage of fuel oil above ground in quantities exceeding 660 gallons (2,498 L) shall comply with NFPA 31 and Chapter 57. 605.4.1.1 Approval. Outdoor fuel oil storage tanks shall be in accordance with UL 80, UL 142 or UL 2085, and also listed as double-wall/secondary containment tanks. 605.4.2.2 Quantity limits. One or more fuel oil storage tanks containing Class II or III combustible liquid shall be permitted in a building. The aggregate capacity of all tanks shall not exceed the following: 1. 660 gallons (2,498 L) in unsprinklered buildings, where stored in a tank complying with UL 80, UL 142 or UL 2085 for Class III liquids, and also listed as a double-wall/secondary containment tank for Class II liquids. 2. 1,320 gallons (4,996 L) in buildings equipped with an automatic sprinkler system in accordance with Section 903.3.1.1, where stored in a tank complying with UL 142 or UL 2085 as a double-wall/secondary containment tank. 3. 3,000 gallons (11,356 L) where stored in protected above-ground tanks complying with UL 2085 and Section 5704.2.9.7 and the room is protected by an automatic sprinkler system in accordance with Section 903.3.1.1. [remainder of Section 605.4.1 and subsections unchanged.] Section 605.2.1.6; add this new section to read as follows: Section 605.2.1.6 Maintenance of Chimneys. All chimneys in multi-family occupancies utilizing solid fuel fireplaces shall have the chimneys inspected and, if needed, cleaned by a state or nationally-recognized/certified chimney sweep on a yearly basis. A report of each of each inspection/cleaning shall be maintained on the premises and available for review at the request of the fire prevention division. All records shall be maintained for a minimum of three years. Section 606.3.3.3: change to read as follows: 606.3.3.3 Records. Records for inspections shall state the individual and company performing the inspection, a description of the inspection and when the inspection took place. Records for cleaning shall state the individual and company performing the cleaning and when the cleaning took place. Such records shall be completed after each inspection or cleaning and maintained. Inspection and cleaning reports stall be submitted to the fire code official using a process promulgated by the fire code official. Section 807.5.2.2 and 807.5.2.3; change to read as follows: 807.5.2.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings, and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with section 807 or be noncombustible. Exception: Corridors protected by an approved automatic fire sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. 807.5.2.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. Section 901.6.1.1; add section to read as follows: 901.6.1.1 Standpipe Testing. Building owners/agents must maintain and test standpipe systems as per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is required every 5 years: 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be backflushed or inspected by approved camera when foreign material is present or when caps are missing, and also hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable pumping system (as approved by the fire code official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm that there are no open hose valves prior to introducing water into a dry standpipe. There are no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. All hose valves shall be exercised. 4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's as required by the fire code official. 5. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative Code, Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of each standpipe riser in the building. The tag shall be check-marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. 6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (fire code official) shall be followed. 7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable, as required by the State Rules mentioned above and NFPA 25. 8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected nighttime freezing conditions. 9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the fire code official. Section 901.6.3.2; add Section 906.3.2 to read as follows: 901.6.3.2 Reports. Inspection, test, and maintenance records shall be submitted to the fire code official using a process promulgated by the fire code official. Section 901.7; change to read as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. Where utilized, fire watches shall be provided with at least one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires. Section 903.1.1; change to read as follows: 903.1.1 Alternative protection. Alternative automatic fire-extinguishing systems complying with Section 904 shall be permitted in addition to automatic sprinkler protection where recognized by the applicable standard, or as approved by the fire code official. Section 903.2; delete the exception and change to read as follows: 903.2 Where required. Approved automatic sprinkler systems shall be provided in the locations described in Sections 903.2.1 through 903.2.12, and as follows: 1. Commercial structures—Automatic sprinkler systems will be required in all newly constructed structures exceeding 3,600 square feet of fire area, any remodel or addition that changes the square footage beyond 3,600 square feet or any single tenant expansion requiring a new certificate of occupancy that exceeds 12,000 square feet of fire area. Whichever requirement listed in this chapter, including exceptions, or defined in this amendment that is more restrictive will apply. Credit will not be given for fire walls with a fire resistive rating in lieu of automatic fire sprinkler systems. 2. Whenever Section 903.2 requires the installation of an approved automatic sprinkler system, the automatic sprinkler system shall be installed throughout the entire structure. Exceptions: 1. In strip mall structures, the installation of fire barrier walls with not less than a two-hour fire resistive rating may be allowed to separate the occupancy from the rest of the building in lieu of providing fire sprinkler protection throughout the entire structure as approved by the fire code official. 2. When a change in Occupancy Classification is required for an existing building or tenant space, the building or tenant space shall comply with the provisions of Section 903.2. Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY - NO STORAGE ALLOWED." Section 903.2.1; change to read as follows: 903.2.1 Group A. An automatic fire sprinkler system shall be installed throughout the entire structure housing a Group A occupancy as provided in this section. Section 903.2.1.1; change to read as follows: 903.2.1.1 Group A-1. An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The floor area exceeds 3,600 square feet of fire area. 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. 4. The fire area contains a multitheater complex. Section 903.2.1.2; change to read as follows: Section 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The floor area exceeds 3,600 square feet. 2. The fire area has an occupant load of 100 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Section 903.2.1.3; change to read as follows: 903.2.1.3 Group A-3. An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The floor area exceeds 3,600 square feet of fire area. 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Section 903.2.1.4; change to read as follows: 903.2.1.4 Group A-4. An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The floor area exceeds 3,600 square feet of fire area. 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Section 903.2.1.6; delete exception and change to read as follows: 903.2.1.6 Assembly occupancies on roofs: Where an occupied roof has an assembly occupancy with an occupant load in excess of 100 persons, all floors between the occupied roof and the level of exit discharge shall be equipped with an automatic fire sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. Section 903.2.2: change to read as follows: Ambulatory care facilities. An automatic fire sprinkler system shall be installed throughout the entire structure containing an ambulatory care facility when any of the following conditions exist: 1. The floor area exceeds 3,600 square feet. 2. Four or more care recipients are incapable of self-preservation, whether rendered incapable by staff or staff has accepted responsibility for care recipients already incapable. 3. One or more care recipients that are incapable of self-preservation are located at other than the level of exit discharge serving such facility. In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire structure. Section 903.2.1.8; add this new section to read as follows: 903.2.1.8 Group B. An automatic sprinkler system shall be provided for Group B occupancies where the floor area exceeds 3,600 square feet of fire area. Section 903.2.3; change to read as follows: 903.2.3 Group E. An automatic sprinkler system shall be provided for Group E occupancies as follows: 1. Where the floor area exceeds 3,600 square feet of fire area. 2. (Unchanged) 3. (Unchanged) Section 903.2.4; change to read as follows: 903.2.4 Group F-1. An automatic sprinkler system shall be provided for Group F-1 occupancies where either: 1. The floor area exceeds 3,600 square feet of fire area; 2. (Unchanged) 3. (Unchanged) 4. (Unchanged) Section 903.2.4.2 to 903.2.4.3; add new sections to read as follows: 903.2.4.2 Group F-1 distilled spirits. An automatic sprinkler system shall be provided throughout a Group F-1 fire area used for the manufacture of distilled spirits involving more than 120 gallons of distilled spirits (>16% alcohol) in the fire area at any one time. 903.2.4.3 Group F-2. An automatic sprinkler system shall be provided for Group F-2 occupancies where the floor area exceeds 3,600 square feet of fire area. Section 903.2.6; change to read as follows: Section 903.2.6 Group I. An automatic fire sprinkler system shall be provided throughout buildings with a Group I fire area conforming to Section 903.3.1.1. Section 903.2.7; change to read as follows: 903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy when the floor area exceeds 3,600 square feet of fire area or for Group M occupancies located more than three stories above grade plane. 903.2.7.1 {No change.} Section 903.2.8; change to read as follows: 903.2.8. Group R. An automatic sprinkler system shall be provided throughout all buildings with a Groups R occupancies and shall include the following criteria: 1. Throughout Groups R-1, 2, and 4 occupancies in all areas, including but not limited to attics, balconies, breezeways, garages and exterior storerooms, shall have an approved hydraulically designed fire sprinkler system installed. 2. Residential or quick response standard sprinklers shall be used in dwelling units and guestroom portions of the building. 3. Attics are to be sprinklered in accordance with NFPA 13 except that allowable sprinkler omissions for attics as outlined in NFPA 13 shall not be allowed. Section 903.2.9; change to read as follows: 903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout where one of the following conditions exists: 1. The floor area exceeds 3,600 square feet of fire area; 2. A Group S-1 occupancy is located more than three stories above the grade plane; or 3. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet. Section 903.2.9.1; change to read as follows: 903.2.9.1 Repair Garages. An automatic fire sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406.8 of the International Building Code, if: 1. The floor area exceeds 3,600 square feet of fire area; or 2. Buildings with repair garages servicing vehicles parked in basements. Section 903.2.9.2; change to read as follows: 903.2.9.2 Bulk storage of tires. Buildings and structures where the area for the storage of tires exceeds 20,000 cubic feet or 3,600 square feet shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Section 903.2.9.3; change to read as follows: 903.2.9.3 Group S-1 distilled spirits or wine. An automatic sprinkler system shall be provided throughout a Group S-1 fire area used for the bulk storage of distilled spirits or wine involving more than 120 gallons of distilled spirits or wine (>16% alcohol) in the fire area at any one time. Section 903.2.9.4; delete the exception. Section 903.2.9.5; add this new section to read as follows: 903.2.9.5 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. Section 903.2.10; delete exception and change section to read as follows: 903.2.10 Group S-2 enclosed parking garages. An automatic fire sprinkler system shall be installed throughout all S-2 occupancies where the fire area exceeds 3,600 square feet. Section 903.2.10.1; change section to read as follows: 903.2.10.1 Commercial parking garages. An automatic fire sprinkler system shall be installed throughout buildings used for storage of commercial motor vehicles where the fire area exceeds 3,600 square feet. Section 903.2.10.3; add section to read as follows: 903.2.10.3 Open Parking Garages. An automatic fire sprinkler system shall be installed throughout all open parking garages. Exception: Automatic fire sprinkler systems are not required when all sides of the open parking garage are separated from adjacent buildings or property lines by a fire apparatus lane conforming to Section 503.2 of this code and no occupancies are located above the subject garage. Section 903.2.11.3; delete exceptions and change to read as follows: 903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed throughout stories with a floor level, other than penthouses in compliance with Section 1510 of the International Building Code, located 35 feet or more above the lowest level of fire department vehicle access, measured to the finished floor. Automatic sprinklers shall be installed throughout all stores to and including the level of exit discharge. Section 903.2.11.7; add this new section to read as follows: 903.2.11.7 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4,572 mm), see Chapter 32 to determine if those provisions apply. Section 903.2.11.8; add this new section to read as follows: 903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire-extinguishing system. Section 903.2.13; add this new section to read as follows: 903.2.13 Historic District. An automatic sprinkler system conforming to Section 903.3.1.1 of this code shall be installed throughout all buildings in the Historic District, regardless of size, use, or occupancy classification, except where otherwise prohibited by law. 1. For purposes of this section only, the Historic District shall include all lots or parcels which adjoin: (a) the north side of West Main Street between and including buildings currently addressed as 101 through 191 West Main Street; (b) the south side of West Main Street between and including buildings currently addressed as 102 through 170 West Main Street; and (c) North Poydras Street. Section 903.3.1.1.1; change to read as follows: 903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance-rated construction or contains electrical equipment. In such locations, an alternative fire suppression or detection system may be required by the fire code official. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the fire code official. 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. 4. Elevator machine rooms, machinery spaces, and hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. Section 903.3.1.2; change to read as follows: 903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in Group R occupancies shall be permitted to be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions: 1. Four stores or less above grade plane. 2. The floor level of the highest story is 35 feet (10,668 mm) or less above the lowest level of fire department vehicle access. 3. The floor level of the lowest story is 35 feet (10,668 mm) or less below the lowest level of fire department vehicle access. {No change to remainder of section.} Section 903.3.1.2.1; change to read as follows: 903.3.1.2.1 Balconies and decks. Sprinkler protection shall be provided for exterior balconies, decks, and ground floor patios of dwelling units and sleeping units, provided there is a roof or deck above. Sidewall sprinklers that are used to protect such areas shall be permitted to be located such that their deflectors are within 1 inch to 6 inches below the structural members and a maximum distance of 14 inches below the deck of the exterior balconies and decks that are constructed of open wood joist construction. Section 903.3.1.2.2; change to read as follows: 903.3.1.2.2 Corridors and balconies. Sprinkler protection shall be provided in all corridors and for all balconies. {Delete the rest of the section} Section 903.3.1.2.3; add this new section to read as follows: 903.3.1.2.3 Attics, Exterior Storerooms, and Attached Garages. Sprinkler protection is required in attic spaces of such buildings' exterior storerooms, and attached garages. Attic automatic fire sprinkler systems shall be installed per NFPA 13. Section 903.3.1.3; change to read as follows: 903.3.1.3 NFPA 13D sprinkler systems. Automatic sprinkler systems installed in one- and two-family dwellings, Group R-3, Group R-4 Condition 1 and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D or in accordance with state law. Section 903.3.1.4; add section to read as follows: 903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section. 903.3.1.4.1 Attics. Only dry-pipe, preaction, or listed antifreeze automatic fire sprinkler systems shall be allowed to protect attic spaces. Exception: Wet-pipe fire sprinkler systems shall be allowed to protect non-ventilated attic spaces where: 1. The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building, and 2. Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard, and 3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level. 903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by the fire code official for small sections of large diameter water-filled pipe. Section 903.3.5; change to read as follows: 903.3.5 Water supplies. Water supplies for automatic sprinkler systems shall comply with this section and the standards referenced in Section 903.3.1. The potable water supply shall be protected against backflow in accordance with the requirements of this section and the International Plumbing Code. For connections to public waterworks systems, the water supply test used for design of fire protection systems shall be adjusted to account for seasonal and daily pressure fluctuations based on information from the water supply authority and as approved by the fire code official. Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a 10 psi safety factor. Reference Section 507.4 for additional design requirements. Section 903.3.8; change to read as follows: 903.3.8 Limited area sprinkler systems. When approved by the fire code official and not in conflict with Section 903.2(2), limited area sprinkler systems shall be in accordance with the standards listed in Section 903.3.1 except as provided in Sections 903.3.8.1 through 903.3.8.5. Section 903.4; change to read as follows: 903.4 Sprinkler system supervision and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and water-flow switches on all sprinkler systems shall be electrically supervised by a listed fire alarm control unit. Exceptions: [All exceptions to remain unchanged] Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. Section 903.4.2; add second paragraph to read as follows: 903.4.2 Alarms. An approved audible device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. Section 903.4.2.1; add this new section to read as follows: 903.4.2.1 Multiple tenant buildings. A minimum of one horn/strobe notification appliance shall be installed in each tenant space of a multiple tenant building to notify occupants of an automatic fire sprinkler system water-flow condition. Section 903.6; change to read as follows: 903.6 Where required in existing buildings and structures. An automatic sprinkler system shall be provided in existing buildings and structures where required in Chapter 11 and, when a change in Occupancy Classification is required for an existing building or tenant space, the building or tenant space shall comply with the provisions of the new Occupancy Classification as stated in Section 903.2. Section 903.7; add this new section to read as follows: 903.7 Fire Control Rooms. A fire control room is required for all new automatic sprinkler system installations. The fire control room shall comply with the following: 1. Located on an exterior wall adjacent to a fire apparatus access lane. 2. Be a minimum size of 5-foot by 7-foot. 3. Shall house the system riser, fire alarm control panel, and spare sprinkler heads. 4. Have an exterior entry door that measures at a minimum 36-inch by 80-inch, and shall be identified as FIRE CONTROL ROOM, with a minimum of 4-inch characters, on the exterior of the door. 5. Be equipped with an exterior horn/strobe device indicating a water-flow alarm. Device shall be located above the FDC, 120-inches above finished floor. 6. The riser shall be located a minimum of 12-inches from any wall. 7. A "Knox" key box shall be located on the exterior of the fire control room, adjacent to the exterior door, installed 5-feet above finished floor, and shall house a key to open the exterior door. 8. Room shall be kept free of any storage. Section 905.2; change to read as follows: 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low supervisory alarm. Section 905.3.9; add this new section to read as follows: 905.3.9 Buildings exceeding 10,000 square feet. In buildings exceeding 10,000 square feet in area per story and any portion of the building's interior is more than 200 feet of travel, vertically and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be provided. Exception: 1. Automatic dry, semi-automatic dry, and manual dry standpipes are allowed as provided for in NFPA 14 where approved by the fire code official. 2. R-2 occupancies of four stories or less in height having no interior corridors. Section 905.4, change to read as follows: 905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official. Exception: {No change.} 2. {No change.} 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Exception: Where floor areas adjacent to an exit passageway are reachable from an exit stairway hose connection by a 30-foot hose stream from a nozzle attached to 100 feet of hose, a hose connection shall not be required at the entrance from the exit passageway to other areas of the building. 4. {No change.} 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located to serve the roof or at the highest landing of a stairway with stair access to the roof provided in accordance with Section 1011.12. 6. {No change.} 7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as otherwise approved by the fire code official. Section 905.8; change to read as follows: 905.8 Dry standpipes. Dry standpipes shall not be installed. Exception: Where subject to freezing and in accordance with NFPA 14. Additionally, manual dry standpipe systems shall be supervised with a minimum 10 psig and a maximum 40 psig air pressure with a high/low supervisory alarm. Section 905.9; change to read as follows: 905.9 Valve supervision. Valves controlling water supply shall be supervised in the open position so that the change in the normal position of the valve will generate a supervisory signal at the supervising station required by Section 903.4. Where a fire alarm system is provided, a signal shall also be transmitted to the control unit. Exceptions: 1. Valve to underground key or hub valves in roadway boxes provided by the municipality or public utility do not require supervision. 2. Valves locked in the normal position and inspected as provided in this code in buildings not equipped with a fire alarm system. Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. Section 906.1 (1); delete exception 3 in its entirety. Section 907.1.4; add new section to read as follows: 907.1.4 Design standards. Where a new fire alarm system is installed, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating devices. Section 907.2.1; change to read as follows: 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with Section 707.3.10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 and the occupant notification appliances will activate throughout the notification zones upon sprinkler water flow. Activation of fire alarm notification appliances shall: 1. Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the walking surface level, and 2. Stop any conflicting or confusing sounds and visual distractions. Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. Section 907.2.3, Exception No. 1; change to read as follows and add a new 1.1 to read as follows: Exceptions: 1. A manual fire alarm system is not required in Group E occupancies with an occupant load of less than 50. 1.1. Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2½ or less years of age, see Section 907.2.6.) Section 907.2.10; change to read as follows: 907.2.10 Group S. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group S public and self-storage occupancies for interior corridors and interior common areas. Visible notification appliances are not required within storage units. Exception: {No change.} Section 907.2.13, Exception 3; change to read as follows: 3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas. Section 907.4.2.; add Section 907.4.2.7 to read as follows: 907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type. Section 907.6.1; add Section 907.6.1.1 to read as follows: 907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from an addressable input (monitor) module may be wired Class B, provided the distance from the addressable module to the initiating device is ten feet or less. Section 907.6.3; delete all exceptions. Section 907.6.6; change to read as follows: Section 907.6.6 Monitoring. Fire alarm systems required by this chapter or by the International Code shall be monitored by an approved supervising station in accordance with NFPA 72. See Section 907.6.3 for the required information transmitted to the supervising station. Section 910.2; add Section 910.2.3 with exceptions to read as follows: 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet in single floor area. Exception: Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as required for a high-hazard commodity classification. Exception: Buildings of noncombustible construction containing only noncombustible materials. Sections 910.3.4.1; add this new section to read as follows: 910.3.4.1 Sprinklered buildings. Where installed in buildings equipped with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically. The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees F greater than the temperature rating of the sprinklers installed. Exception: Manual only systems per Section 910.2. Sections 910.3.4.2; add this new section to read as follows: 910.3.4.2 Nonsprinklered buildings. Where installed in buildings not equipped with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 100°F and 220°F above ambient. Exception: Listed gravity-operated drop out vents. Section 910.4.3.1; change to read as follows: 910.4.3.1 Makeup Air. Makeup air openings shall be provided within 6 feet (1,829 mm) of the floor level. Operation of makeup air openings shall be automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m2 per 0.4719 m3/s) of smoke exhaust. Section 912.2; add second sentence as follows: Fire department connections shall be located within 50 feet of a fire apparatus access road as the fire hose lays along an unobstructed path. Section 912.2.3 add to read as follows: 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the fire department connection as the fire hose lays along an unobstructed path. Section 912.3.1; add this new section to read as follows: 912.3.1 Multiple inlet fire department connections. When more than two, 2½-inch Siamese connections are required for a fire department connection, in addition to the required 2½-inch Siamese connections, a 5-inch Storz fitting shall be installed at a 45-degree downward angle at the end of the fire department connection manifold. Section 913.2.1; change to read as follows: 913.2.1 Protection of fire pump rooms. Rooms where fire pumps are located shall be separated from all other areas of the building in accordance with Section 913.2.1 of the International Building Code. When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft.—8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1. Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by Section 506.1. Section 914.3.1.2; change to read as follows: 914.3.1.2 Water supply to required fire pumps. In buildings that are more than 120 feet in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: Two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through no fewer than one of the connections. Section 1006.2.1; change Exception #3 to read as follows: 1006.2.1 Egress based on occupant load and common path of egress travel. Two exits or exit doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or space shall be determined in accordance with 1004.2. Exceptions: 1. {No change.} 2. {No change.} 3. Unoccupied rooftop mechanical rooms and penthouses are not required to comply with the common path of egress travel distance measurement. 4. Section 1009.8; add new exception 7 to read as follows: 7. Buildings regulated under State Law and built in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009 and Chapter 11. Section 1010.2.5, amend exceptions 3 and 4 as follows: 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S occupancy, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf. The inactive leaf shall contain no doorknobs, panic bars, or similar operating hardware. 4. Where a pair of doors serves a Group A, B, F, M or S occupancy, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress width requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. Section 1020.2 Construction; add Exception 6 to read as follows: 6. In unsprinklered group B occupancies, corridor walls and ceilings need not be of fire-resistive construction within a single tenant space when the space is equipped with approved automatic smoke-detection within the corridor. The actuation of any detector shall activate self-annunciating alarms audible in all areas within the corridor. Smoke detectors shall be connected to an approved automatic fire alarm system where such system is provided. Section 1030.1.1.1; add Exception #4 to read as follows: Exceptions: 1. through 3. {No change.} 4. Where alternate means or methods are submitted to and approved by the Building and Fire Code Officials. Section 1032.2; change to read as follows: 1032.2 Reliability. Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Section 1103.3; change to read as follow: 1103.3 Existing elevators. Existing elevators, escalators, and moving walks shall comply with the requirements of Sections 1103.3.1 and 1103.3.2 and provide emergency signage as required by Section 606.3. Section 1103.5.1: add sentence to read as follows: Fire sprinkler system installation shall be completed within 24 months from date of notification by the fire code official. Section 1103.5.6; add this new section to read as follows: 1103.5.6 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with Section 2404. Section 1103.7; add Section 1103.7.7 and 1103.7.7.1 to read as follows: 1103.7.7 Fire alarm system design standards. Where an existing fire alarm system is upgraded or replaced, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke and/or heat detectors shall have analog initiating devices. Exception: Existing systems need not comply unless the total building, or fire alarm system, remodel or expansion exceeds 30% of the building. When cumulative building, or fire alarm system, remodel or expansion initiated after the date of original fire alarm panel installation exceeds 50% of the building, or fire alarm system, the fire alarm system must comply within 18 months of permit application. 1103.7.7.1 Communication requirements. Refer to Section 907.6.6 for applicable requirements. Section 1203; change and add to read as follows: 1203.1.1 {No change.} 1203.1.2 {No change.} 1203.1.3 Installation. Emergency power systems and standby power systems shall be installed in accordance with the International Building Code, NFPA 70, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval, except as specified in Chapter 11. 1203.1.4 {No change.} 1203.1.5 Load Duration. Emergency power systems and standby power systems shall be designed to provide the required power for a minimum duration of 2 hours without being refueled or recharged, unless specified otherwise in this code. Exception: Where the system is supplied with natural gas from a utility provider and is approved. 1203.1.6 through 1203.1.9 {No changes to these sections.} 1203.1.10 Critical Operations Power Systems (COPS). For Critical Operations Power Systems necessary to maintain continuous power supply to facilities or parts of facilities that require continuous operation for the reasons of public safety, emergency management, national security, or business continuity, see NFPA 70. 1203.2 Where Required. Emergency and standby power systems shall be provided where required by Sections 1203.2.1 through 1203.2.26 or elsewhere identified in this code or any other referenced code. 1203.2.1 through 1203.2.3 {No change.} 1203.2.4 Emergency Voice/alarm Communications Systems. Emergency power shall be provided for emergency voice/alarm communications systems in the following occupancies, or as specified elsewhere in this code, as required in Section 907.5.2.2.5. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72. Covered and Open Malls, Section 907.2.20 and 914.2. Group A Occupancies, Sections 907.2.1 and 907.5.2.2. Special Amusement Buildings, Section 907.2.12 and 914.7. High-rise Buildings, Section 907.2.13 and 914.3. Atriums, Section 907.2.14 and 914.4. Deep Underground Buildings, Section 907.2.19 and 914.5. 1203.2.5 through 1203.2.14 {No change.} 1203.2.15 Means of Egress Illumination. Emergency power shall be provided for means of egress illumination in accordance with Sections 1008.3 and 1104.5.1. (90 minutes) 1203.2.16 Membrane Structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with Section 3103.12.6. (90 minutes) Standby power shall be provided for auxiliary inflation systems in permanent membrane structures in accordance with Section 2702 of the International Building Code. (4 hours) Auxiliary inflation systems shall be provided in temporary air-supported and air-inflated membrane structures in accordance with section 3103.10.4. 1203.2.17 {No change.} 1203.2.18 Smoke Control Systems. Standby power shall be provided for smoke control systems in the following occupancies, or as specified elsewhere in this code, as required in Section 909.11: Covered Mall Building, International Building Code, Section 402.7 Atriums, International Building Code, Section 404.7 Underground Buildings, International Building Code, Section 405.8 Group I-3, International Building Code, Section 408.4.2 Stages, International Building Code, Section 410 Special Amusement Buildings (as applicable to Group A's), International Building Code, Section 411.1 Smoke Protected Seating, Section 1030.6.2. 1203.2.19 {No change.} 1203.2.20 Covered and Open Mall Buildings. Emergency power shall be provided in accordance with Section 907.2.19 and 914.2.3. 1203.2.21 Airport Traffic Control Towers. A standby power system shall be provided in airport traffic control towers more than 65 ft. in height. Power shall be provided to the following equipment: 1. Pressurization equipment, mechanical equipment and lighting. 2. Elevator operating equipment. 3. Fire alarm and smoke detection systems. 1203.2.22 Smokeproof Enclosures and Stair Pressurization Alternative. Standby power shall be provided for smokeproof enclosures, stair pressurization alternative and associated automatic fire detection systems as required by the International Building Code, Section 909.20.7.2. 1203.2.23 Elevator Pressurization. Standby power shall be provided for elevator pressurization system as required by the International Building Code, Section 909.21.5. 1203.2.24 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be provided when eliminating the smoke dampers in ducts penetrating shafts in accordance with the International Building Code, Section 717.5.3, exception 2.3. 1203.2.25 Common Exhaust Systems for Clothes Dryers. Standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures in accordance with the International Mechanical Code, Section 504.10, Item 7. 1203.2.26 Means of Egress Illumination in Existing Buildings. Emergency power shall be provided for means of egress illumination in accordance with Section 1104.5 when required by the fire code official. (90 minutes in I-2, 60 minutes elsewhere.) 1203.3 through 1203.6 {No change.} Section 2304.1; change to read as follows: 2304.1 Supervision of dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be in accordance with the following: 1. Conducted by a qualified attendant; and/or, 2. Under the supervision of a qualified attendant; and/or, 3. An unattended self-service facility in accordance with Section 2304.3. At any time the qualified attendant of item Number 1 or 2 above is not present, such operations shall be considered as an unattended self-service facility and shall also comply with Section 2304.3. Section 2401.2; delete this section. Section 3103.3.1; delete this section. Table 3206.2, footnote h; change text to read as follows: h. Where storage areas are protected by either early suppression fast response (ESFR) sprinkler systems or control mode special application sprinklers with a response time index of 50 (m·s) ½ or less that are listed to control a fire in the stored commodities with 12 or fewer sprinklers, installed in accordance with NFPA 13, manual smoke and heat vents or manually activated engineered mechanical smoke exhaust systems shall be required within these areas. Table 3206.2, footnote j; add footnote j to row titled "High Hazard" and "Greater than 300,000" to read as follows: j. High hazard high-piled storage areas shall not exceed 500,000 square feet. A 2-hour fire wall constructed in accordance with Section 706 of the International Building Code shall be used to divide high-piled storage exceeding 500,000 square feet in area. Section 3206.9; change to read as follows: 3206.9 Fire department hose connections. Where exit passageways are required by the International Building code for egress, a Class I standpipe system shall be provided in accordance with Section 905. Whenever access doors are required by Section 3206.7, a Class I, automatic wet or automatic dry standpipe system shall be provided on the building's interior, adjacent to each access door. Section 3311.1; change to read as follows: SECTION 3311 ACCESS FOR FIRE FIGHTING AND EMERGENCY RESPONSE 3311.1 Required access. Approved vehicle access for fire-fighting and emergency response shall be provided to all construction or demolition sites. Vehicle access shall be provided to within 100 feet (15,240 mm) of temporary or permanent fire department connections. Vehicle access shall be provided by either temporary or permanent roads, capable of supporting the imposed vehicle load of 85,000 GVW under all weather conditions. Surface shall be either concrete or asphalt. Vehicle access shall be maintained until permanent fire apparatus access roads are available. When fire apparatus access roads are required to be installed for any structure or development, they shall be approved prior to the time of which construction has progressed beyond completion of the foundation of any structure. Whenever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by a sign approved by the fire code official. Section 5601.1.3; change to read as follows: 5601.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited within the city limits and to a distance of 5,000 from the city limits of the City of Lewisville, except within any portion of such 5,000-foot area which is contained within the territory of any other municipal corporation. Exceptions: 1. When approved for fireworks displays, storage and handling of fireworks as allowed in Sections 5604 and 5608. 2. The use of fireworks for approved fireworks displays as allowed in Section 5608. 3. The sale of fireworks outside the city limits. Section 5703.6; change to read as follows: 5703.6 Piping systems. Piping systems, and their component parts, for flammable and combustible liquids shall be in accordance with Sections 5703.6.1 through 5703.6.11. An approved method of secondary containment shall be provided for underground tank and piping systems. Section 5704.2.11.4; change to read as follows: 5704.2.11.4 Leak prevention. Leak prevention for underground tanks shall comply with Sections 5704.2.11.4.1 through 5704.2.11.4.3. An approved method of secondary containment shall be provided for underground tank and piping systems. Section 5704.2.11.4.2; change to read as follows: 5704.2.11.4.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFPA 30 and as specified in Section 5704.2.11.4.3. Section 5704.2.11.4.3; add this new section to read as follows: 5704.2.11.4.3 Observation wells. Approved sampling tubes of a minimum 4 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling tube at the corners of the excavation with a minimum of 4 tubes. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required. Section 5707.4; add paragraph to read as follows: Mobile fueling sites shall be restricted to commercial, industrial, governmental, or manufacturing, where the parking area having such operations is primarily intended for employee vehicles. Mobile fueling shall be conducted for fleet fueling or employee vehicles only, not the general public. Commercial sites shall be restricted to office-type or similar occupancies that are not primarily intended for use by the public. Section 6103.2.1.8; add this new section to read as follows: 6103.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20-pound water capacity. Aggregate capacity shall not exceed 60-pound water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. Section 6107.4; change to read as follows: 6107.4 Protecting Containers from Vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in accordance with Section 312. Section 6106.13; delete exception and change to read as follows: 6109.13 Protection of Containers. LP-gas containers shall be stored within a suitable enclosure or otherwise protected against tampering. Vehicle impact protection shall be provided as required by Section 6107.4. Table B105.1 (1); change chart to amend the following: For fire-flow calculation area of 3,601 and greater system or with automatic fire sprinkler system as required in Section 903.3.1.3 of the International Fire Code or Section P2904 of the International Residential Code, the minimum fire flow shall be 1,000 gallons per minute. Table B105.2; change footnote (a) to read as follows: a. The reduced fire-flow shall not be less than 1,500 gallons per minute. Table B105.2: change chart to amend the following: The minimum fire-flow requirement for buildings with automatic sprinkler systems designed per Sections 903.3.1.1 and 903.3.1.2 shall be 50% of the value in Table B105.1(2) but in no case shall be less than 1,500 gallons per minute. Add Appendix O to read as follows: Appendix O: Certificates of Inspection for Commercial and Industrial Occupancies Section O101 Scope. The fire code official is authorized to administer certificates of inspection. The fire code official is authorized to enter and examine buildings and commercial and industrial occupancies in accordance with Section 104.3 for the purpose of enforcing this code. Section O102 Definitions. O102.1 Definitions. For the purpose of this appendix, the following words and phrases have the meanings respectively ascribed to them by this subsection: Certificate of inspection. Certificate of Inspection issued by the fire code official pursuant to this appendix demonstrating compliance with this code issued on an annual basis. Premises. A lot, plot or parcel of land, including any structure thereon, and grounds and facilities held out for the use of tenants generally and any other area or facility whose use is promised to the tenant. Section O103 Inspection or Reinspection. O103.1 Inspection. Prior to the city's issuance of a certificate of inspection, duly authorized members of the city fire prevention division shall perform an inspection in accordance with Section 108 of this code. An inspection shall not be required more than once per year, except as provided for in Section 108 of this code. Should the City perform an annual inspection less than twelve (12) months after the previous annual inspection, the next annual inspection date will be one year from the last annual inspection date. O103.2 Reinspection. If at the time of inspection, the occupancy is found not to be in compliance with this code, a reinspection shall be required. After notification of the violations which were detected during the initial inspection, the owner, agent, or occupant shall be required to remedy the conditions of violation. A citation may be issued for each violation. The occupant, owner, or agent shall be notified of a time at which reinspection shall occur. The date for the first reinspection shall not be more than 30 days from the time of the original inspection. The date for any subsequent reinspection shall be not more than 10 days from the time of the last inspection. Should the City perform a reinspection under this section, the next annual inspection date will be one year from the last reinspection date. Section O104 Inspection Fee and Reinspection Fee. O104.1 Inspection Fees. The fee for an inspection shall be in accordance with the current adopted fee schedule for the city. Said fee shall be due upon completion of the inspection. Should the City perform an annual inspection less than twelve (12) months after the previous annual inspection, a pro-rated inspection fee shall be charged. O104.2 Reinspection fee. A fee for an inspection that is required to verify that a violation has been repaired or corrected shall be in accordance with the current adopted fee ordinance for the city. Said fee shall be due upon completion of the reinspection. Section O105 Certificate of Inspection Required. O105.1 Certificate of Inspection Compliance. No commercial or industrial occupancy may operate its business without a certificate of inspection. The owner, agent, or occupant operating a business without a certificate of inspection shall, upon conviction in a court of competent jurisdiction, be guilty of a misdemeanor, and each day that such owner, agent or occupant shall fail to obtain said permit shall constitute a separate offense. O105.2 Valid Certificate of Inspection. If no hazardous conditions or violations of the fire code are detected at the time of the inspection or reinspection, a certificate of inspection shall be issued upon payment of the inspection fee and any reinspection fee(s). The certificate of inspection shall include the name and address of each owner, the location and type of occupancy, and the owner, agent, or occupant's signature. O105.3 Termination of Certificate of Inspection. A change in use or occupancy terminates the existing certificate of inspection, and a new certificate of inspection shall be required. O105.4 Revocation of Certificate of Inspection. Any certificate of inspection issued under this code may be revoked when it is determined after a hearing by the fire chief that: 1. It is used by a person other than the person to whom the certificate was issued; 2. It is used for a location other than that for which it was issued; 3. Any of the conditions or limitations set forth in the certificate have been violated; 4. The possessor of the certificate fails, refuses, or neglects to comply with any order or notice served upon him under the provisions of this code within the time period provided therein; or 5. There are false statements or misrepresentations of material fact in the plans, specifications, or documentation upon which the certificate of inspection was based.

(Ord. No. 4040-12-2013, § 4, 12-16-13; Ord. No. 4098-08-2014, § 2, 8-4-14; Ord. No. 4273-05-2016, § 3, 5-2-16; 0005-18-ORD, § 1, 1-8-18; 0202-20-ORD, §§ 1, 2, 4-6-20; 0243-20-ORD, § 3, 8-17-20; ; 0471-22-ORD, § IV(Exh. C), 6-6-22; 0613-23-ORD, § 2, 11-6-23)

Ask a question about Lewisville law

Corpus searches the Lewisville sections it holds and shows the ones that match, with their citations. Free, no sign-in.