Sec. 100-122. Power distribution lines.
(a) Main power lines not located underground shall be suspended at least 18 feet above the ground. There shall be a minimum horizontal clearance of three feet between overhead wiring and any mobile home, service building or other structure. (b) All direct burial conductors or cable shall be buried at least 18 inches below the surface and shall be insulated and specially designed for the purpose. Such conductors shall be located not less than one foot radial distance from water, sewer, gas or communication lines. (Ord. No. 711, 11-11-69)