For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 100-122 — Power distribution lines

Code of Ordinances of the City of Longview, Texas (June 2026; current through Ordinances 4635 passed 06.25.26) · Longview City Code § 100-122

Corpus is an independent public-information project, not the official City of Longview website. Stable reference: corpuslaw.us/code/01099ce8-0e73-490a-a7d2-9eb7378b4bf7

Sec. 100-122. Power distribution lines.

(a) Main power lines not located underground shall be suspended at least 18 feet above the ground. There shall be a minimum horizontal clearance of three feet between overhead wiring and any mobile home, service building or other structure. (b) All direct burial conductors or cable shall be buried at least 18 inches below the surface and shall be insulated and specially designed for the purpose. Such conductors shall be located not less than one foot radial distance from water, sewer, gas or communication lines. (Ord. No. 711, 11-11-69)

Ask a question about Longview law

Corpus searches the Longview sections it holds and shows the ones that match, with their citations. Free, no sign-in.