§ 28.10.054 — Approved backflow prevention device assembly and installation
Code of Ordinances of the City of Lubbock, Texas (Lubbock Code of Ordinances, Charter and Unified Development Code current through Ordinance 2026-O0123 adopted September 22, 2026 (eCode360 publication LU6396, scraped 2026-11-17)) · Lubbock Code of Ordinances § 28.10.054
Corpus is an independent public-information project, not the official City of Lubbock website. Stable reference: corpuslaw.us/code/9a0330d5-9dc1-4d13-bb09-79f3529bd64e
§ 28.10.054: Approved backflow prevention device assembly and installation.
(a) Any backflow prevention assembly required by sections 28.10.052, 28.10.053, or 28.10.054 of the Code of Ordinances of the city, or section 312.9 or 608 of the 2021 International Plumbing Code, or sections P2503.7 or P2902 of the 2021 International Residential Code, or the USC Manual of Cross-Connection Control, American Water Works Association M14 Manual, as applicable, shall be of a model and size approved by the water purveyor/building official or as approved by 30 TAC 290.47(i), as same may be amended from time to time. Backflow prevention devices must be approved by the city prior to installation. A plumbing permit is required in accordance with section 28.05.001 of this chapter. The city shall determine the type and location of the backflow prevention assembly to be installed within the area served by the public water system. (b) The term "approved backflow prevention assembly" shall mean a backflow prevention assembly that has been manufactured and installed in full conformance with the standards specified within the 2021 International Plumbing Code and those established by the American Water Works Association (AWWA) and the USC Manual of Cross-Connection Control, American Water Works Association M14 Manual, titled: AWWA C510 Standard for Double Check Valve Backflow-Prevention Assembly, and AWWA C511 Standard for Reduced-Pressure Backflow-Prevention Assembly, and have met completely the laboratory field performance specifications of the Foundation for Cross-Connection Control and Hydraulic Research (FCCHR) and the University of Southern California (USC), "Specification of Backflow-Prevention Assemblies" - Section 10 of the most current issue of the Manual of Cross-Connection Control. (c) Backflow prevention assemblies shall be installed in a manner designed to facilitate ease of testing and inspection by the city or any certified general tester. All backflow prevention assemblies shall be tested upon installation, relocation, or repair of same. (d) Backflow prevention assemblies, in addition to other requirements set forth in sections 28.10.052, 28.10.053, or 28.10.054 of the Code of Ordinances of the city, or section 312.9 or 608 of the 2021 International Plumbing Code, sections P2503.7 or P2902 of the 2021 International Residential Code, or the USC Manual of Cross-Connection Control, American Water Works Association M14 Manual, shall be installed in accordance with subsections (1) through (9) below. The clearance standards set forth in subsections (1) through (9), below, shall apply to all assemblies installed in enclosures and meter boxes. (1) Backflow prevention assemblies that are larger than four inches and installed more than five feet above floor level must have a suitable platform for use by testing or maintenance personnel. (2) All backflow prevention assemblies installed eight feet or higher above floor level must have installed a suitable permanent ladder for use by testing or maintenance personnel. (3) All backflow prevention assembly enclosures shall be designed for ready access and sized to allow for the minimum clearance as established in this article. Removable protective enclosures may be installed on smaller assemblies. (4) Reduced pressure zone assemblies two inches and smaller shall have at least a six-inch clearance on both ends and on top of the assembly. Additionally, there shall be twelve inches of clearance below the relief valve and twelve inches of clearance on the test cock side of the assembly. All assemblies larger than two inches shall have a minimum of twelve inches of clearance on the back side, twenty-four inches of clearance on the test cock side, and the relief valve opening shall be at least twelve inches plus nominal size of assembly above the floor or highest possible water level. (5) Double check valve assemblies larger than two inches may be installed above finished grade in a freeze-proof enclosure or below grade in a vault. If assembly is installed below grade, the test cocks must be plugged with corrosion resistant watertight plugs, and shall be no less than twelve inches below grade with a minimum of twelve inches clearance below the backflow assembly device. There shall be at least a six-inch clearance on both ends of the assembly with a minimum clearance of twelve inches on the back side and twenty-four inches on the test cock side. The top of the vault shall be two inches above ground level. Double check valve assemblies shall be installed so that the checks are horizontal. (6) Double check valve assemblies two inches and smaller may be installed above finished grade in a freeze-proof enclosure or below grade in a box. If assembly is installed below grade, the test cocks must be plugged with corrosion resistant watertight plugs, and shall be no less than twelve inches below grade with a minimum of twelve inches clearance below the backflow assembly device. There shall be at least a six-inch clearance on both ends of the assembly with a minimum clearance of twelve inches on the back side and twelve inches on the test cock side. The top of the box shall be two inches above ground level. Double check valve assemblies shall be installed so that the checks are horizontal. (7) Bypass arrangements are prohibited. Pipefittings which could reasonably be calculated to constitute a means by which a backflow assembly could be bypassed and defeated shall not be installed. (8) All facilities that require continuous, uninterrupted water service and are required to have a backflow assembly must make provision for the parallel installation of assemblies of the same type so that testing, repair and maintenance can be performed. (9) All health hazard facilities shall have containment from the city's potable water system. For the purposes of this subsection, "containment" shall mean protection of the public water supply at the service connection.
( 1983 Code, sec. 6-100.3 ; Ordinance 2005-O0001 , sec. 5, adopted 1/27/2005 ; Ordinance 2007-O0056 , sec. 5, adopted 6/14/2007 ; Ordinance 2009-O0033 , sec. 5, adopted 4/27/2009 ; Ordinance 2011-O0104 , sec. 1, adopted 11/3/2011 ; Ordinance 2016-O0073 adopted 5/12/16 ; Ordinance 2020-O0017 adopted 2/11/2020 ; Ordinance 2024-O0026 adopted 3/26/2024 )
Ask a question about Lubbock law
Corpus searches the Lubbock sections it holds and shows the ones that match, with their citations. Free, no sign-in.