For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 28.13.019 — When bushing or receptacle required

Code of Ordinances of the City of Lubbock, Texas (Lubbock Code of Ordinances, Charter and Unified Development Code current through Ordinance 2026-O0123 adopted September 22, 2026 (eCode360 publication LU6396, scraped 2026-11-17)) · Lubbock Code of Ordinances § 28.13.019

Corpus is an independent public-information project, not the official City of Lubbock website. Stable reference: corpuslaw.us/code/48c50852-60ca-4f9e-a451-49b688827887

§ 28.13.019: When bushing or receptacle required.

A bushing or receptacle of a recognized type shall be provided where electric-discharge tubing passes through a sheet-metal wall or partition of an outdoor sign or an indoor sign operating at a potential higher than seven thousand five hundred (7,500) volts, unless the tubing is supported so as to positively maintain a spacing of not less than one-fourth (1/4) inch between the tubing and the grounded metal where the tubing passes through the wall or partition.

( 1983 Code, sec. 6-313 ; Ordinance 8856 , sec. 2, adopted 12/12/1985 )

Ask a question about Lubbock law

Corpus searches the Lubbock sections it holds and shows the ones that match, with their citations. Free, no sign-in.