§ 28.15.004 — Amendments
Code of Ordinances of the City of Lubbock, Texas (Lubbock Code of Ordinances, Charter and Unified Development Code current through Ordinance 2026-O0123 adopted September 22, 2026 (eCode360 publication LU6396, scraped 2026-11-17)) · Lubbock Code of Ordinances § 28.15.004
Corpus is an independent public-information project, not the official City of Lubbock website. Stable reference: corpuslaw.us/code/f7168c0d-d075-468e-9929-fbe4bc5ee38c
§ 28.15.004: Amendments.
(a) Sloped roofs. Section 306.5.1 is hereby amended to read as follows: 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of 6 units vertical in 12 units horizontal (50 percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. Access shall not require walking on roofs having a slope greater than 6 units vertical in 12 units horizontal (50 percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with ladders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the International Building Code in the path of travel to and from appliances, fans or equipment requiring service. (b) Auxiliary drain pan. Section 307.5 is hereby amended to read as follows: 307.5 Auxiliary drain pan. Category IV condensing appliances shall be provided with an auxiliary drain pan where damage to any building component will occur as a result of stoppage in the condensate drainage system. Such pan will be installed in accordance with the applicable provisions of Section 307 of the International Mechanical Code. (c) Protection methods against corrosion. Section 404.11.2 is hereby amended to read as follows: 404.11.2 Protection methods. Underground piping shall comply with one or more of the following: 1. The piping shall be made of corrosion-resistant material that is suitable for the environment in which it will be installed. 2. Pipe shall have a factory-applied, electrically-insulating coating. Fittings and joints between sections of coated pipe shall be coated in accordance with the coating manufacturer's instructions. 3. The piping shall have a cathodic protection system installed and the system shall be monitored and maintained in accordance with an approved program. 4. Approved protective coatings or wrap may be field installed if piping that has a factory-applied, electrically-insulating coating is not readily available. (d) Located at manifold. Section 409.5.3 is hereby amended to read as follows: 409.5.3 Located at manifold. Where the appliance shutoff valve is installed at a manifold, such shutoff valve shall be located within 50 feet (15,240 mm) of the appliance served and shall be readily accessible and permanently identified. The piping from the manifold to within 6 feet (1829 mm) of the appliance shall be designed, sized and installed in accordance with Sections 401 through 408. Shutoff valves located within attic spaces shall not be considered readily accessible. (e) Pressure regulators. Section 410.1 is hereby amended to read as follows: 410.1 Pressure regulators. A line pressure regulator shall be installed where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80/CSA 6.22. Access shall be provided to pressure regulators. Regulators shall be located near walkways or at an access point. Pressure regulators shall be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. (f) Log lighters. Section 603 is hereby deleted in its entirety. (g) Exhaust material. Section 614.4 is hereby amended to read as follows: 614.4 Exhaust installation. Exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums unless properly sleeved with materials conforming to Section 602.2.1 of the International Mechanical Code (in the case of plenums), or with materials meeting the requirements for class 0 or 1 duct materials (in the case of ducts). Backdraft dampers shall not be required for vertical terminations through the roof. (h) Protection required. Section 614.8 is hereby amended to read as follows: 614.8 Protection required. Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all framing members where there is less than 1.25 inches (32 mm) between the duct and the finished face of the framing member. Such shield plates shall have a thickness of not less than 0.0575 inch (1.463 mm) (No. 16 gage). Such plates shall cover the area of the duct where the member is notched or bored.
( 1983 Code, secs. 6-605–6-609 ; Ordinance 2009-O0035 , sec. 1, adopted 4/27/2009 ; Ordinance 2011-O0105 , sec. 1, adopted 11/3/2011 ; Ordinance 2016-O0075 adopted 5/12/16 ; Ordinance 2019-O0090 adopted 7/23/2019 ; Ordinance 2024-O0030 adopted 3/26/2024 )
Ask a question about Lubbock law
Corpus searches the Lubbock sections it holds and shows the ones that match, with their citations. Free, no sign-in.
