§ 22-108 — When metallic conduit required
Code of Ordinances, City of McAllen, Texas (through Ord. 2026-83 adopted 2026-08-24) · McAllen Code of Ordinances § 22-108
Corpus is an independent public-information project, not the official City of McAllen website. Stable reference: corpuslaw.us/code/02bc1f61-484d-4cac-8065-a1fa1a18f6d9
§ 22-108: When metallic conduit required.
(a) All of the following electrical wiring for lights, heat, power or other purposes installed within the city shall in all cases be contained and encased in metallic conduit: (1) All electric wiring in buildings of any description situated in the first fire zone. (2) All electric wiring in buildings of a construction known in the building trade as "fireproof" or "slow burning." (3) All electric wiring on all service installations, and such wiring shall be continuous from entrance to main line switch and from main line switch to distribution cabinet, unless approved S.E. cable is used. (b) A nonmetallic conduit is permitted if the building is not located in a fire zone district.
( 1966 Code, § 13-44 )