§ 10-79 — Use-Specific Maximum Sound Levels for Data Centers and Battery Energy Storage Systems
Code of the City of Mesquite, Texas (Supp. No. 71: codified through Ordinance No. 5259, enacted July 20, 2026) · Mesquite City Code § 10-79
Corpus is an independent public-information project, not the official City of Mesquite website. Stable reference: corpuslaw.us/code/bded076f-9be0-4286-afd7-c430b5ddc80e
Sec. 10-79. - Use-Specific Maximum Sound Levels for Data Centers and Battery Energy Storage Systems.
(a) Applicability. Notwithstanding Table 02 (Maximum Permissible Sound Levels) of Sec. 10-75, subsection (a), the maximum permissible sound levels in this Sec. 10-79 apply to all Data Center facilities regulated under Mesquite Zoning Ordinance (MZO) Section 3.514 (Date Centers), and to BESS facilities regulated under MZO Section 3.515 (Battery Energy Storage Systems - BESS). For such facilities, the sound levels in this Sec. 10-79 supersede Table 02 for the noise zone in which the Data Center or BESS is located. All other provisions of this Article — including definitions, measurement methodology, affirmative defenses, abatement study requirements, and variance procedures — apply to Data Centers and BESS. (b) Data Centers — Maximum Permissible Sound Levels. Noise from all activities associated with a Data Center, including cooling equipment, fans, air handling units, and generators, shall not exceed the following levels, measured at the property line of the Data Center or at the exterior wall of the nearest occupied residential structure, whichever produces the higher reading: Measurement Location | Daytime 7:00 a.m. - 10:00 p.m. | Nighttime 10:01 p.m. - 6:59 a.m. At any nonresidential property line | 65 dB(A) | 60 dB(A) At any residential property line; or residential district boundary; or adjacent to *protected uses. *See MZO, Part 3, 3.500, 3.514.(Data Centers), Subsection L.(Noise Standards). | 65 dB(A) | 55 dB(A) (c) Battery Energy Storage Systems — Maximum Permissible Sound Levels. Noise from all BESS operational equipment, including cooling systems, inverters, and fans, shall not exceed the following levels, measured at the property line or at the exterior wall of the nearest occupied residential structure, whichever produces the higher reading: Measurement Location | Daytime 7:00 a.m. - 10:00 p.m. | Nighttime 10:01 p.m. - 6:59 a.m. At any nonresidential property line | 60 dB(A) | 55 dB(A) At any residential property line or residential district boundary | 55 dB(A) | 50 dB(A) (d) Low Frequency and Infrasound Noise . In addition to the A-weighted limits in this subsection, low frequency noise from Data Center and BESS operations shall not exceed the following octave-band sound pressure levels, evaluated in accordance with ANSI S12.9 Part 4, Annex D (or most current edition), at the property line nearest the noise source or the exterior wall of the nearest occupied residential structure, whichever produces the higher reading: Octave Band Center Frequency | Maximum (dB re 20 µPa) 16 Hz | 55 dB 31.5 Hz | 55 dB 63 Hz | 55 dB Low frequency noise measurements shall be performed using a Class 1 integrating sound level meter (per IEC 61672) with 1/1 octave band filters (per IEC 61260) and 1/3 octave band filters (per IEC 61260), by or under the direct supervision of a licensed professional engineer specializing in acoustics or an engineer Board Certified by the Institute of Noise Control Engineers. Such measurement and analysis shall additionally evaluate infrasonic content at one-third octave band center frequencies below twenty (20) Hz. (e) Measurement Methodology. All noise measurements conducted for purposes of demonstrating compliance with or enforcing the sound levels in this subsection (e) shall comply with the following requirements: (1) All measurements shall report both A-weighted decibel levels (dBA) and C-weighted decibel levels (dBC). (2) All measurements shall include full octave band (1/1 octave) spectral analysis using a Class 1 integrating sound level meter (per IEC 61672) with 1/1 octave band filters (per IEC 61260). (3) All measurements shall include one-third octave band (1/3 octave) spectral analysis using equipment meeting the requirements of IEC 61260. (4) All measurements shall include a tonality assessment evaluating whether any noise source produces perceptible pure tones, conducted in accordance with ISO 1996-2 (or most current edition) or an equivalent method. (5) All measurements shall be performed by or under the direct supervision of a licensed professional engineer specializing in acoustics or an engineer Board Certified by the Institute of Noise Control Engineers. (6) These measurement requirements apply to pre-construction noise studies, post-construction compliance studies, and any enforcement measurements taken by or on behalf of the City. (f) Background Level Exception. The background sound level exception in subsection (b) applies to measurements taken under this subsection (e). (g) Exemptions. The maximum permissible sound levels of this subsection do not apply to: (1) Demolition or construction activities authorized under a valid building permit; or (2) Emergency situations arising from sudden, reasonably unforeseen events beyond the control of the facility operator requiring emergency generator use; or (3) Routine generator testing conducted in compliance with the testing schedule established as a condition of CUP approval under Section 3.514.(Data Centers), M.3 of the Mesquite Zoning Ordinance. (h) Enforcement. Violation of the sound levels in this subsection constitutes a noise disturbance under Section 10-71(a)(3). A Data Center or BESS facility that exceeds these limits shall be subject to the noise abatement study requirements of Section 10-77. A Data Center or BESS operator seeking relief from these limits may apply for a noise variance to the Board of Adjustment in accordance with Section 10-78(b). Approval of a noise variance does not modify any Conditional Use Permit condition established under the Mesquite Zoning Ordinance. (i) Coordination with Mesquite Zoning Ordinance. The use-specific sound levels in this subsection are consistent with and implement the noise standards in MZO Section 3.514. (Data Centers), Subsection L. (Noise Standards); and 3.515. (Battery Energy Storage Systems - BESS), Subsection S. (Noise Standards). In the event of a conflict regarding noise regulations in any section of the Mesquite City Code, including the MZO, the more restrictive standard shall apply.
(Ord. No. 5259, § 2(Exh. C), 7-20-26)
Ask a question about Mesquite law
Corpus searches the Mesquite sections it holds and shows the ones that match, with their citations. Free, no sign-in.