§ 5-5-44: Sprinkler system.

The fire marshal shall review, approve and stamp the approved plans after the sprinkler system has been tested by an underground hydro which must conducted, with the sprinkler system pressured at 200 PSI and it must hold pressure for a minimum of two (2) hours. (1) The fire marshal shall receive all required documentation for the underground flush, underground and aboveground hydro in order to pass inspection. (2) The sprinkler system shall be certified by the sprinkler company with a tag indicating the installation date and sprinkler company’s information (3) The sprinkler system must be placed in LIVE mode, connected to and monitored with the fire alarm system.

( Ordinance 2020-07 adopted 2/25/20 )