Sec. 12-71. - Minimum grounding systems.
As a minimum, two (2) vertically driven ground rods shall be provided for each electrical service to a building. If these ground rods project above grade, they shall be installed so as not to create personnel hazards from tripping or impalement and also to minimize likelihood of damage from lawn care equipment to the rods, grounding electrode conductors and connectors. Additional, supplemental grounding systems may be allowed. Specialized general grounding systems such as grid type and for specialized purposes such as lightning protection must be inspected and approved by a Texas Registered Professional Engineer. A project specific letter certifying acceptable design and installation of additional, supplemental grounding systems shall be submitted to the City of Pasadena Inspection Department.
(Ord. No. 17-009, § 1(Exh. A), 1-17-17)