§ 44-185 — Fire systems
Code of Ordinances, City of Round Rock, Texas (Supp. 27: codified through Ordinance of August 13, 2026 (online updated November 5, 2026)) · Round Rock Code of Ordinances § 44-185
Corpus is an independent public-information project, not the official City of Round Rock website. Stable reference URL
Sec. 44-185. - Fire systems.
(a) An approved DCDA or RPDA shall be installed on fire sprinkler systems comprised of piping material that is not approved for potable water use and/or that does not provide for periodic flow-through during each 24-hour period, unless a variance has been granted in writing by the director. A RPDA must be installed if any solution or substance other than the potable water may be introduced into the sprinkler system. (b) Upon the approved installation of a DCDA or RPDA, a cross connection test report completed by a city registered, licensed fireline tester must be sent to the director, and such report must include the information required by this article.
(Code 1995, § 10.713; Ord. No. O-2015-2423, § I, 5-14-2015)