Sec. 7-22. - Code Amendments.

The following parts of 2023 National Electrical Code are amended: Subsection 230.30 is amended to read as follows: 230.30. Installation. (A) All direct buried cables and conductors shall be installed in an approved conduit or raceway. (B) Insulation. Underground service conductors shall be insulated for the applied voltage. Exception: A grounded conductor shall be permitted to be uninsulated as follows: (1) Bare copper used in a raceway (2) Bare copper for direct burial where bare copper is approved for the soil conditions (3) Bare copper for direct burial without regard to soil conditions where part of a cable assembly identified for underground use (4) Aluminum or copper-clad aluminum without individual insulation or covering where part of a cable assembly identified for underground use in a raceway or for direct burial (C) Wiring Methods. Underground service conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods: (1) RMC conduit (2) IMC conduit (3) Type NUCC conduit (4) HDPE conduit (5) PVC conduit (6) RTRC conduit (7) Type IGS cable (8) Type USE conductors or cables (9) Type MV or Type MC cable identified for direct burial applications (10) Type MI cable where suitably protected against physical damage and corrosive conditions (11) Type TC-ER cable where identified for service entrance use and direct burial applications Subsection 230.42 is amended to read as follows: 230.43. Wiring Methods for 1000 Volts, Nominal, or Less. (A) Service-entrance conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods: (1) Open wiring on insulators (2) Type IGS cable (3) Rigid metal conduit (RMC) (4) Intermediate metal conduit (IMC) (5) Electrical metallic tubing (EMT) (6) Electrical nonmetallic tubing (7) Service-entrance cables (8) Wireways (9) Busways (10) Auxiliary gutters (11) Rigid polyvinyl chloride conduit (PVC) (12) Cablebus (13) Type MC cable (14) Mineral-insulated, metal-sheathed cable, Type MI (15) Flexible metal conduit (FMC) not over 1.8 m (6 ft) long or liquidtight flexible metal conduit (LFMC) not over 1.8 m (6 ft) long between a raceway, or between a raceway and service equipment, with a supply-side bonding jumper routed with the flexible metal conduit (FMC) or the liquidtight flexible metal conduit (LFMC) according to 250.102(A), (B), (C), and (E) (16) Liquidtight flexible nonmetallic conduit (LFNC) (17) High density polyethylene conduit (HDPE) (18) Nonmetallic underground conduit with conductors (NUCC) (19) Reinforced thermosetting resin conduit (RTRC) (20) Type TC-ER cable where identified for use as service entrance conductors (21) Flexible bus systems (B) Commercial Service Riser Raceways on Utility Poles and Structures. Where service-entrance conductors of 1000 volts, nominal, or less are installed in a raceway that is above grade and fastened to a utility-owned pole or structure and the installation is not under the exclusive control of an electric utility as described in 90.2(D)(5), the raceway shall be rigid metal conduit (RMC) in accordance with Article 344. The use of polyvinyl chloride (PVC) conduit (Schedule 40 or Schedule 80) for this riser is prohibited. 1. The RMC shall be raintight and continuous from all points above finished grade to the service head or weatherhead. 2. The RMC shall be securely fastened to the pole or structure in accordance with 344.30 and supported to prevent damage. 3. Bonding and grounding shall comply with 250.92 and 250.94, and shall comply with the Utility providers standards (Center Point). 4. Raceway fittings and bushings shall be listed and installed in accordance with 344.42. Informational Note: Coordination with the serving electric utility may be required for attachment methods and clearances. Installations under the utility's exclusive control are outside the scope of the NEC per 90.2(D)(5). Paragraph 300.5(D) is amended to read as follows: (D) Protection from Damage. Direct buried conductors and cables shall be installed in an approved conduit or raceway. Table 300.5 is amended to read as follows: Table 300.5 Minimum Cover Requirements, 0 to 1000 Volts, Burial in Inches LOCATION OF WIRING METHOD OR CIRCUIT | TYPE OF WIRING METHOD OR CIRCUIT Column 1 Direct Burial Cables or Conductors | Column 2 Rigid Metal Conduit or Intermediate Metal Conduit | Column 3 Nonmetallic Raceways Listed for Direct Burial Without Concrete Encasement or Other Approved Raceways | Column 4 Residential Branch Circuits Rated 120 Volts or Less With GFCI protection and Maximum Overcurrent Protection of 20 Amperes | Column 5 Circuits for Control of Irrigation and Landscape Lighting Limited to Not More Than 30 Volts and Installed with Type UF or in Other Identified Cable or Raceway All locations not specified below | 24 c | 6 | 18 | 12 | 6 a, b In trench below 2-inch-thick concrete or equivalent | 18 c | 6 | 12 | 6 | 6 Under a building | 0 (In raceway only or Type MC identified for direct burial) | 0 | 0 | 0 (In raceway only or Type MC identified for direct burial) | 0 (In raceway only or Type MC identified for direct burial) Under minimum of 4-inch-thick concrete exterior slab with no vehicular traffic and the slab extending not less than 6 inches beyond the underground installation | 18 c | 4 | 4 | 6 (Direct burial) 4 (In raceway) | 6 (Direct burial) 4 (In raceway) Under streets, highways, roads, alleys, driveways and parking lots | 24 c | 24 | 24 | 24 | 24 One- and two-family dwelling driveways and outdoor parking areas, and used only for dwelling-related purposes | 18 c | 18 | 18 | 12 | 18 In solid rock where covered by minimum of 2 inches concrete extending down to rock | 2 (In raceway only) | 2 | 2 | 2 (In raceway only) | 2 (In raceway only) a. A lesser depth shall be permitted where specified in the installation instructions of a listed low-voltage lighting system. b. A depth of 6 inches shall be permitted for pool, spa, and fountain lighting that is installed in a nonmetallic raceway, limited to not more than 30 volts and part of a listed low-voltage lighting system. c. Direct buried cables or conductors shall be installed in an approved conduit or raceway. Notes: 1. Cover is defined as the shortest distance in inches measured between a point on the top surface of any direct-buried conductor, cable, conduit or other raceway and the top surface of finished grade, concrete, or similar cover. 2. Raceways approved for burial only where encased concrete shall require concrete envelope not less than 2 inches thick. 3. Lesser depths shall be permitted where cables and conductors rise for terminations or splices or where access is otherwise required. 4. Where one of the wiring method types listed in Columns 1 through 3 is combined with one of the circuit types in Columns 4 and 5, the shallower depth of burial shall be permitted. 5. Where solid rock prevents compliance with the cover depths specified in this table, the wiring shall be installed in metal or nonmetallic raceway permitted for direct burial. The raceways shall be covered by a minimum of 2 inches of concrete extending down to the rock. Subsection 351.12 is amended to read as follows: 352.12. Uses Not Permitted. PVC conduit shall not be used under the conditions specified in 352.12(A) through (F). (A) Hazardous (Classified) Locations. In any hazardous (classified) location, except as permitted by other articles of this code. (B) Support of Luminaires. For the support of luminaires or other equipment not described in 352.10(I). (C) Physical Damage. Where subject to physical damage, except as permitted in 352.10(K). (D) Ambient Temperatures. Where subject to ambient temperatures in excess of 50°C (122°F) unless listed otherwise. (E) Theaters and Similar Locations. In theaters and similar locations, except as provided in 518.4 and 520.5. (F) Service Riser on Utility Poles. PVC conduit, including Schedule 80, shall not be used as the above-ground service riser raceway where fastened to a utility-owned pole or structure.

(Ord. No. 2395, § 4, 1-20-26)

Ask a question about Sugar Land law

Corpus searches the Sugar Land sections it holds and shows the ones that match, with their citations. Free, no sign-in.