§ 13-3200 — Special requirements for battery energy storage systems
Code of the City of Chesapeake, Virginia (Supp. No. 148: codified through Ordinance No. 26-O-071, enacted August 11, 2026) · Chesapeake Zoning Ordinance § 13-3200
Corpus is an independent public-information project, not the official City of Chesapeake website. Stable reference: corpuslaw.us/code/d2600217-6e72-434b-b798-6941b127d52c
§ 13-3200. - Special requirements for battery energy storage systems.
A. Intent. The purpose of this ordinance is to protect public health, safety, and welfare by providing a regulatory framework for the construction of battery energy storage systems, ensuring compatible land uses around battery energy storage systems, and mitigating the impacts of battery energy storage systems. B. Definitions. The following words, terms, and phrases shall have the following definitions when used in this ordinance: 1. Battery energy storage system means one or more devices, individually or assembled together, capable of collecting and storing energy in order to distribute electricity at a future time, provided the storage system is a primary use on the property. 2. Fire code means the fire code sections of the USBC, the Virginia Statewide Fire Prevention Code, and Chapter 34 of the Chesapeake City Code, all as may be amended from time to time. 3. NFPA means the National Fire Protection Association. 4. USBC means the Virginia Uniform Statewide Building Code codified in Chapter 6, Title 36 (§ 36-97 et seq.) of the Code of Virginia, 1950, as amended. C. Applicability. The requirements of this section shall apply to all battery energy storage systems installed within the city after the effective date of this ordinance and to pre-existing battery energy storage systems upon expansion, modification, or a change of use pursuant to article 15 of this ordinance. D. Plans, studies, agreements, and sureties. In addition to any other requirement stated in applicable law, every application for a conditional use permit to operate a battery energy storage system shall include the following: 1. Emergency response plan. An emergency response plan that includes, at a minimum: a. Procedures for safe shutdown, de-energizing, or isolation of equipment and systems under emergency conditions to reduce the risk of fire, electric shock, and personal injuries, and for safe start-up following cessation of emergency conditions; b. Procedures for inspection and testing of associated alarms, interlocks, and controls; c. Procedures to be followed in response to notifications from the battery energy storage system, when provided, that could signify potentially dangerous conditions, including shutting down equipment, summoning service and repair personnel, and providing agreed upon notification to fire department personnel for potentially hazardous conditions in the event of a system failure; d. Emergency procedures to be followed in case of fire, explosion, release of liquids or vapors, damage to critical moving parts, or other potentially dangerous conditions. Procedures may include sounding the alarm, notifying the fire department, evacuating personnel, de-energizing equipment, and controlling and extinguishing the fire; e. Response considerations similar to a safety data sheet (SDS) that will address response safety concerns and extinguishment when an SDS is not required; f. Procedures for dealing with battery energy storage system equipment damaged in a fire or other emergency event, including maintaining contact information for personnel qualified to safely remove damaged battery energy storage system equipment from the facility; g. A water containment plan; h. Other procedures as determined necessary by the city to provide for the safety of occupants, neighboring properties, and emergency responders; and i. Procedures and schedules for conducting drills of these procedures and for training local first responders on the contents of the plan and appropriate response procedures. 2. Decommissioning agreement. Prior to approval of a conditional use permit, the applicant/owner shall enter into a written decommissioning agreement with the city to be implemented upon abandonment of, or cessation of activities at, the battery energy storage system. This written agreement shall include, at a minimum, the following terms and conditions: a. A narrative description of the battery energy storage system equipment and uses, the decommissioning process, a stated timeframe within which the site will be decommissioned, and the estimated costs for decommissioning. Such narrative description shall be prepared by a professional engineer licensed in the Commonwealth of Virginia who has experience preparing decommissioning estimates; b. The estimated costs for decommissioning the battery energy storage system shall be sufficient to secure the proper and lawful decommissioning of the site, including a reasonable allowance for estimated administrative costs related to a default and an annual inflation factor; and c. Upon cessation or abandonment of the battery energy storage system the applicant/owner shall safely remove and properly dispose of all battery energy storage system equipment, facilities, and devices and restore the property to its pre-use condition. 3. Financial assurance. The applicant/owner shall provide the city with financial assurance based upon the estimated costs for decommissioning as required herein. a. The financial assurance may be in the form of certified funds, cash escrow, bond, or irrevocable letter of credit, subject to the approval of the city attorney or designee. b. If the applicant/owner of a battery energy storage system breaches the obligations in the written decommissioning agreement, then the city may utilize the financial assurance required herein, in whole or in part, to enter the property and engage in decommissioning the site without the applicant/owner's consent. Any portion of the financial assurance not utilized by the city may be released only upon compliance with the following: i. Cessation of all operations of the battery energy storage system; ii. Complete decommissioning of the site; iii. Final site inspection and approval of the decommissioned site by the director of development and permits or designee; iv. Certification that all inspections and approvals required under applicable state or federal law have been obtained; and v. Submission of a written document, signed by the applicant/owner, indemnifying the city against any and all costs, fines, penalties, or damages resulting from any environmental pollution which arose, or may arise, out of the design, construction, operation, maintenance, decommissioning, or abandonment of the battery energy storage system. E. Design and installation standards. In addition to any other applicable site plan and design requirements in this zoning ordinance, any battery energy storage system shall, at a minimum, adhere to the following requirements and standards: 1. Required setbacks. a. As established by fire industry best practices for a safe perimeter and a "cold zone", and to protect and preserve the health, safety, and welfare of persons, neighboring property, and the overall quality of life in Chesapeake, any battery energy storage system shall be setback three hundred (300) feet from all property lines. b. Any setback from a street shall be measured from the reservation line established in accordance with the city's adopted Master Transportation Plan. Where a reservation line cannot be established under the provisions of the adopted Master Transportation Plan, the setback shall be measured as provided for in section 19-202. c. City council may reduce the distance required by this section to a distance of no less than one hundred (100) feet if: i. The applicant for a battery energy storage system provides an independent risk analysis of the proposed battery energy storage system and site; ii. The independent risk analysis identifies sufficient safety and fire protection systems and features of the battery energy storage system and site; and iii. Council determines that the risk of harm to nearby persons and property is lessened due to the information provided in the independent risk analysis. 2. Layered fire protection. Any battery energy storage system shall include a sufficient layered fire protection approach, as determined by the Chesapeake Fire Department, which may include, without limitation: a. Adequate primary and secondary emergency access to and within the battery energy storage system facility and all properties within a three hundred (300) foot radius of the battery energy storage system; b. Fixed water sources, such as fire hydrants that meet distance and fire-flow demand as required by the Chesapeake Fire Department; c. An appropriate combination of four-hour rated fire walls between individual battery energy storage units and sufficient spacing between units to minimize the risk of a fire spreading to multiple battery energy storage units; d. Prompt condition monitoring and alarming, with remote and on-site notifications, for early detection of a fire event; e. Infrared camera(s) to monitor thermal levels of the battery energy storage system; f. Automatic detection of any off-gassing of flammable or combustible gas and an ignition or sparking system to consume off-gassing prior to an unsafe level of buildup thereof; g. Automatic deflagration venting to release gas, smoke, flame, or pressure and avoid containing unsafe levels thereof; h. Remote monitoring of all systems and alerts to ensure prompt corrective action, whether conducted remotely or on site; and i. A site designed to contain runoff of water, fire protection agents, and other chemicals. 3. Any battery energy storage system shall comply with all applicable industry standards as well as federal, state, and local laws, regulations, and ordinances. 4. Whenever it is feasible and prudent to do so, as determined by the director of development and permits or designee, onsite transmission or power lines shall be placed underground. The director of development and permits, or designee, may waive this requirement and allow for above ground transmission or power lines when the same is required by site design, geography, topography, or other relevant considerations. 5. All onsite lighting shall be arranged and installed so that the direct or reflected illumination does not exceed one-half (0.5) footcandles above background measured at the lot line of any adjoining property. All lighting shall be directed away from adjoining properties and public rights-of-way to reduce glare and interference. F. Operation. A battery energy storge system shall be operated in accordance with all applicable law, policies, standard manuals, and industry best practices as they all may be amended from time to time. This includes, but is not limited to: 1. Fire code; 2. The USBC; 3. City standard policies and manuals; 4. NFPA and other industry best practices, including but not limited to NFPA 855, UL 9540, and UL 9540A; and 5. All other applicable sections of the City Codes. G. Transfer of ownership. Within thirty (30) days of a change in at least fifty (50) percent of ownership or control of a battery energy storage system, the owner shall notify the zoning administrator and the city council of such change. This notification shall include: 1. The name, address, and contact information for the new owner and designee in the Commonwealth of Virginia; and 2. Written proof, subject to the review and approval of the city attorney or designee, that the new owner has been advised of and agreed in writing to comply with: a. This zoning ordinance; b. The decommissioning agreement; and c. All stipulations associated with the conditional use permit.
(Ord. No. 23-O-109, 11-28-23)
Ask a question about Chesapeake law
Corpus searches the Chesapeake sections it holds and shows the ones that match, with their citations. Free, no sign-in.