§ 13-201 — Maximum standpipe outlet pressure

Code of the City of Richmond, Virginia, 2026 (Recodification codified through Ordinance No. 2025-207, adopted October 14, 2025) · Richmond, Va., City Code § 13-201

Corpus is an independent public-information project, not the official City of Richmond website. Stable reference: corpuslaw.us/code/d903be8e-ad3a-4b63-a297-7ed2a81c2bba

Sec. 13-201. - Maximum standpipe outlet pressure.

The owner, manager or person in control of a building, structure or premises equipped with adjustable pressure reducing valves on a firefighting standpipe system, shall set the maximum outlet pressure for no more than 125 PSI residual pressure during full flow. Each standpipe outlet valve shall be tested at least every five years to ensure that the maximum flow discharge pressure does not exceed 125 PSI during full flow. Test records shall be provided to the Fire Code Official. Nonadjustable standpipe discharge valves with outputs over 150 PSI shall have permanent signs reading expected pressure. Pressure reducing valves installed after July 1, 2015, shall be set with maximum 125 PSI residual pressure during full flow.

(Code 2015, § 13-201; Code 2020, § 13-201; Ord. No. 2015-205, § 1, 1-11-2016)