Sec. 34-28. - Recirculation systems.

(a) Filter room. Type 2 pools shall be provided with a structure or room to contain the filtration equipment, pumps and other recirculation system appurtenances, and disinfection equipment. The room shall be finished in a light color and be constructed of materials which are impervious to water and chemicals necessary for the operation of the pool. Adequate illumination of twenty (20) footcandles measured twenty-four (24) inches (61 centimeters) above floor level, shall be provided. The floor of the filter room shall be designed to provide for an adequate drainage with a minimum floor slope of 1:50 and a maximum of 1:24 to the drain and shall be kept dry, particularly in the vicinity of electrical panels. The filter room shall be adequately cross-ventilated, which may, upon the decision of the administrative authority, require mechanical ventilation and all equipment shall be installed so that it is convenient to operate and repair. Adequate headroom shall be provided above all filters. The provision of any facility for discharging filter backwashing water into the filter room floor is prohibited. The room shall be provided with a door(s) of sufficient width to permit the removal of equipment, and shall be capable of being secured against entry by unauthorized persons. The entrance to the filter room shall be adjacent to the pool area or so located that the operator can enter the room without having to exit the enclosed pool area. (b) Filters. The recirculation system shall be equipped with a filtration system that will filter the entire contents of the pool at the required rate. Filtration equipment shall be operated continuously twenty-four (24) hours per day, unless a variance has been granted by the administrative authority to allow the filtration equipment to operate less frequently, as provided in section 34-28.1. Design criteria for the indicated type of filters shall be as follows: (1) Rapid sand filter. A filter utilizing sand as the filter media, with filtration flow rate not exceeding three (3) gallons per minute per square foot (122 liters per minute per square meter) of filter area. The backwash rate of flow shall be three (3) times the filtration rate. (2) Anthracite filter. A filter utilizing anthracite as a filter media, with filtration flow rate not exceeding three (3) gallons per minute per square foot (122 liters per minute per square meter) of filter area. The backwash rate of flow shall be three (3) times the filtration rate. (3) High rate filter. A filter utilizing a media capable of filtration at a high rate of flow. The rate of flow shall be greater than five (5) gallons per minute per square foot (203.7 liters per minute per square meter) of filter area. The backwash rate of flow shall be the same as filtration rate. (4) Diatomaceous earth filter. A filter utilizing diatomaceous earth as a filter media. There are two (2) types of these filters. a. Pressure or vacuum-type. A diatomaceous earth filter through which the rate of flow does not exceed two (2) gallons per minute per square foot (81.5 liters per minute per square meter). b. Pressure or vacuum-type with slurry feeder. A filter equipped to continuously feed a diatomaceous earth suspension and having a rate of flow not to exceed three (3) gallons per minute per square foot (122 liters per minute per square meter). A backwash sump pit with a stand pipe shall be installed to collect spent diatomaceous earth so that it can be collected and disposed of with solid waste. Any other method for accomplishing this may be submitted for consideration. Other filtration systems which are equal to or better than those described above may be used in a pool recirculation system with the approval of the administrative authority. (c) Gauges. Gauges shall be installed as required, on all filter systems to readily indicate the operating pressures of recirculating systems. All gauges shall measure pressure directly in pounds per square inch or kilograms per square meter and shall have an indicator at least two (2) inches (5.08 centimeters) in diameter. (d) Rate of flow indicators. The recirculating system shall be equipped with a rate of flow indicator, which has been approved by the administrative authority, and is located to visibly indicate the rate of flow. The indicator shall read in gallons per minute or liters per minute and shall be located to indicate the rate of flow of filtered water being returned to the pool. The indicator shall be of fixed calibration and properly sized so as to indicate the designed rate of flow at approximately midscale. (e) Hair and lint strainer. At all installations where it is possible for water from the pool to pass through the filters, a strainer shall be provided on the suction side of the pump to prevent hair, lint and other matter from reaching the pump and filters. Strainers shall be corrosion-resistant with openings not over one-eighth (⅛) inch in size providing a free flow area at least four (4) times the area of the pump suction line at the strainer connection and shall be accessible for frequent cleaning.

(Ord. No 2351, 10-17-95; Ord. No. 2995, 7-17-07; Ord. No. 3233, 5-22-12)

Ask a question about Virginia Beach law

Corpus searches the Virginia Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.