§ 14.10.050 — Size—Compliance with Standards

Code of Ordinances of the City of Kennewick, Washington (Codified through Ordinance No. 26-6253, enacted September 15, 2026 (Supp. No. 19)) · Kennewick Municipal Code § 14.10.050

Corpus is an independent public-information project, not the official City of Kennewick website. Stable reference: corpuslaw.us/code/ce4e0653-6ef3-4f98-b594-5d74e7f077b7

14.10.050: - Size—Compliance with Standards.

No water mains smaller than six inches in diameter may be installed unless there exists no reasonable possibility for the water main to be extended, no hydrants will be connected to said water main, and at no point in the installed water main will have a static pressure below 40 pounds per square inch and a residual pressure of 30 pounds per square inch at the applicable fire flow requirements as specified by the City Fire Marshall.

(Ord. 5923, Sec. 1, 8-17-2021)