§ 15.08.100 — Subsection 903.2.10.3 Amended—Buildings 36 Feet or More in Height

Code of Ordinances of the City of Kennewick, Washington (Codified through Ordinance No. 26-6253, enacted September 15, 2026 (Supp. No. 19)) · Kennewick Municipal Code § 15.08.100

Corpus is an independent public-information project, not the official City of Kennewick website. Stable reference: corpuslaw.us/code/52803476-b196-4a16-bfc5-5fa3b7fccc09

15.08.100: - Subsection 903.2.10.3 Amended—Buildings 36 Feet or More in Height.

An approved automatic sprinkler system shall be installed throughout buildings with a floor level having an occupant load of 30 or more that is located 36 feet or more above the lowest level of fire department vehicle access or four stories or more in height. Exceptions: 1. Airport control towers; 2. Open parking structures; 3. Occupancies in Group F-2.

(Ord. 5048 Sec. 1(part), 2004; Ord. 3664 Sec. 9, 1995; Ord. 2490 Sec. 2(part), 1980; Ord. 2083 Sec. 1(part), 1977)