§ 15.41.080 — Types of Backflow Prevention Assemblies and Devices Required

Code of Ordinances of the City of Kennewick, Washington (Codified through Ordinance No. 26-6253, enacted September 15, 2026 (Supp. No. 19)) · Kennewick Municipal Code § 15.41.080

Corpus is an independent public-information project, not the official City of Kennewick website. Stable reference: corpuslaw.us/code/dae9c467-7981-45ee-91dd-e1c4a02dd5c0

15.41.080: - Types of Backflow Prevention Assemblies and Devices Required.

The type of prevention assembly or device required by Section 15.41.070 depends on the degree of hazard which exists. In locations where the Cross-Connection Specialist determines that there is a high health cross-connection hazard the appropriate approved backflow preventer shall be one of the following: AG, RPBA, or RPDA. In locations where the Cross-Connection Specialist determines that there is a low health cross-connection hazard, the appropriate approved backflow preventer shall be one of the following: AG, RPBA, RPDA, DCVA, or DCDA. In addition the following requirements shall apply: (1) All backflow prevention assemblies shall be models included on the current list of backflow prevention assemblies approved for use in Washington State. (2) Backflow prevention assemblies that can pass testing, but are not currently approved by the department, may be used if the assemblies: (a) Were included on the list of approved backflow prevention assemblies at the time of installation; (b) Have been properly maintained; (c) Are commensurate with the purveyor's assessed degree of hazard; and (d) Have been inspected and tested at least annually and have successfully passed the annual tests. (3) An unlisted backflow prevention assembly will be replaced by an approved assembly commensurate with the degree of hazard, when the unlisted assembly: (a) Does not meet the conditions specified in (2)(a) through (2)(d) of this subsection; (b) Is moved; or (c) Cannot be repaired using spare parts from the original manufacturer. (4) All AVBs shall meet the definition of approved atmospheric vacuum breakers as described in the definitions of this chapter. (5) An air-gap separation or reduced pressure backflow assembly shall be installed where the water supply may be contaminated by sewage, industrial waste of a toxic nature or other contaminant which would cause a health or system hazard. (6) In the case of a substance which may be objectionable but not hazardous to health, a double-check valve assembly, air-gap separation or a reduced pressure backflow assembly shall be installed. (7) Lawn sprinkler systems, which are supplied by city water only, shall be required to have either a double check valve assembly, one pressure vacuum breaker assembly, or atmospheric vacuum breakers may be installed on each line. The units shall be approved by the Department of Health, as manufactured. Installation shall be as follows: (a) Pressure Vacuum Breaker Assembly. The pressure vacuum breaker assembly must be installed at least 12 inches above the highest fixture or point of water usage and in such a manner that drainage will preclude back pressure. The pressure vacuum breaker assembly shall be installed vertically with test cocks and control valves accessibly located for connection of test equipment. This assembly is not to be installed more than 60 inches high. (b) Atmospheric Vacuum Breaker. The atmospheric vacuum breaker (AVB) shall be installed on the discharge side of the last valve on each sprinkler zone. The AVB shall be installed at least six inches above the highest head so at no time will the vacuum breaker be subjected to back pressure or drainage. The AVB shall not be installed where it will be under continuous operating pressure for more than 12 hours in any 24-hour period. The AVB unit shall be installed vertically.

(Ord. 3996 Sec. 6, 2001; Ord. 3435 Sec. 3, 1993; Ord. 2700 Sec. 2, 1982; Ord. 2681 Sec. 1(part), 1982; Ord. 2490 Sec. 9(part), 1980; Ord. 2318 Sec. 1(part), 1979)

Ask a question about Kennewick law

Corpus searches the Kennewick sections it holds and shows the ones that match, with their citations. Free, no sign-in.