§ 3.02.390 — Amendment to IFC Subsection 5704.3.4 – Quantity limits for storage, by addition of a new Subsection 5704.3.4.5 – Liquids for demonstration, treatment and laboratory work
Municipal Code, City of Tacoma, Washington (Tacoma Municipal Code current through legislation adopted 2026-09-30 (eCode360 publication TA6977, scraped 2026-11-18)) · Tacoma Municipal Code § 3.02.390
Corpus is an independent public-information project, not the official City of Tacoma website. Stable reference: corpuslaw.us/code/2746e75d-b304-4ace-844d-de799034000d
§ 3.02.390: Amendment to IFC Subsection 5704.3.4 – Quantity limits for storage, by addition of a new Subsection 5704.3.4.5 – Liquids for demonstration, treatment and laboratory work.
5704.3.4.5 Liquids for demonstration, treatment and laboratory work. In Group A, B, E, F, I, M, R, and S occupancies, quantities of flammable and combustible liquids used for demonstration, treatment, and laboratory work exceeding ten gallons shall be stored in liquid storage cabinets in accordance with Section 5704.3.2. Quantities not exceeding ten gallons shall be in approved containers in approved locations.
(Repealed and reenacted by Ord. 28364 Ex. A, 2016-06-14 )